6.5.3 DC output connections - single component distribution
2.4kW rectifier systems only
When attaching cables directly to the output bars, use appropriately sized cables terminated with crimp lugs with
M6 bolts on 5/8" centers.
Remove the bolts and washers at both positive and negative output bars. Bolts are M6 × 1.0 × 16. Note: PEM
nuts are installed into the bus bar for easier installation.
Use the fasteners removed from the previous step to secure the positive and negative cables to the shelf output
bars. Install all fasteners
finger tight
.
Use a “Tongue and Groove” or similar pliers to hold and stabilize the output bar, torque each bolt to 10.85Nm (8
ft-lbf).
The shelf is intended to operate as four independent outputs. Ensure that the controller connected has all load
balancing, and power save features disabled.
WARNING!
Do not complete the final live connections to the battery. Leave open and insulate the final
connections or remove the battery fuses. Switch off the battery contacts if used.
Figure 11 —
19 inch shelf with single component distribution