0100037-J0 Rev D
20
User Guide
Cordex HP 2.4kW / 3.0kW Modular Switched Mode Rectifier
4.2.12 High voltage shutdown (HVSD)
This feature protects the load from over-voltages originating in the rectifiers. The offending rectifier module is shut
down when a high output voltage condition occurs. The red Alarm (Module Fail) LED will illuminate. The module
will restart automatically. However, if more than three over-voltage conditions occur within one minute, the module
will latch off and remain shut down until it is reset by restarting the rectifier via the controller.
4.2.13 Battery eliminator operation
Rectifier modules maintain all specifications (except where indicated) with or without a battery or a DC source
attached in parallel to the output. Under these conditions there will be no monitoring or control activity if AC power
failure occurs.
4.2.14 Distribution
Bulk
• 23 inch 1RU universal mount 12,000/15,000W P/N 0300057-001
• 19 inch 1RU universal mount 9,600/12,000W P/N 0300040-001
Separate feed IO
19 inch 1RU universal mount 4 × 2,400W P/N 0300040-002
Figure 4 —
23 inch or 19 inch shelf with bulk distribution busbars
Figure 5 —
19 inch shelf with single component distribution