23
0100037-J0 Rev D
User Guide
Cordex HP 2.4kW / 3.0kW Modular Switched Mode Rectifier
6. Installation
The equipment is suitable for installation in Network Telecommunication Facilities.
WARNING!
This system is designed to be installed in a restricted access location that is inaccessible to the
general public.
The following procedure is written for qualified personnel to install this product in a clean and dry environment. For
the battery installation, refer to the manufacturer’s manual.
6.1 Installation overview
1. Install shelf in a standard EIA relay rack
2. Connect the shelf chassis ground
3. DC output connections
4. AC input connection
5. Communication cabling (optional)
6.
Verify AC and power the recifier shelf
7. Check battery polarity and connections
8. Final tests
6.2 Safety precautions
Refer to
before beginning this installation.
6.3 Installation tools
Various insulated tools are essential for the installation. Use this list as a guide:
• Battery lifting apparatus if required
•
Electric drill with hammer action, 1/2" capacity
• Various crimping tools and dies to match lugs used in installation
•
Load bank of sufficient capacity to load largest rectifier to its current limit
• Digital voltmeter equipped with test leads
• Cable cutters
•
Torque wrench: 1/4" drive, 0 - 150 in-lb
•
Torque wrench: 3/8" drive, 0 - 100 ft-lb
•
Insulating canvases as required (1' x 1', 2' x 2', 3' x 3')
• Various insulated hand tools including:
- Combination wrenches - Ratchet and socket set
- Various screwdrivers
- Electricians knife
• Battery safety spill kit required for wet cells
• Wire cutters and strippers (14 AWG to 22 AWG) [2.5 to 0.34 mm²]
Summary of Contents for Cordex HP CXRF 48-2.4kW