6.5.1 Busbar connection
Multiple shelves can be connected directly to customers’ vertical busbar.
1.
Remove the bolts and washers at both positive and negative output bars. Bolts are 3/8-16 × 1", and can
accommodate up to 1/4" thick busbar.
2. Use fasteners removed from the previous step to secure the vertical busbars to shelf positive and negative
output bars. Install all fasteners
finger tight
, then apply 27.12Nm (20 ft-lbf) torque to each bolt.
6.5.2 Cable connection
When attaching cables directly to the output bars, use appropriately sized cables terminated with crimp lugs with
3/8" holes on 1" centers.
1.
Remove the bolts and washers at both positive and negative output bars. Bolts are 3/8-16 × 1".
2. Use fasteners removed from the previous step to secure the positive and negative cables to the shelf output
bars. Install all fasteners
finger tight
.
3.
Use a “Tongue and Groove” or similar pliers to hold and stabilize the output bar, torque each bolt to 27.12Nm
(20 ft-lbf).
CUSTOMERS' VERTICAL
BUS BAR, NEGATIVE (-)
CUSTOMERS' VERTICAL
BUS BAR, POSITIVE (+)
INSTALL ALL FASTENERS "FINGER TIGHT",
THEN APPLY 20 ft-lbf TORQUE TO EACH BOLT
Figure 9 — Connecting output bars to customer's vertical busbars
Figure 10 —
Connecting output bars directly to cables
TONGUE AND GROOVE
PLIER TO STABILIZE
THE BAR WHEN
TORQING WIRE LUG
TORQUE TO 20 ft-lbf
NOTE
In a power system, up to five rectifier shelves may be stacked before a gap must be left for
adequate cooling of the rectifiers and shelves.