2.5 Monitoring Options
Monitoring Options
The DCX LP unit also includes monitoring features for local and remote
status indication:
y
Basic control panel version: LED indicators “ON-LINE”, “OFF-
LINE”, “OPTION STATUS”, “EPO TRIPPED”. Alarm contacts:
Form-C relay contacts to provide breaker trip status. See Figure 2.
y
ON-LINE: The battery string is connected – circuit breaker/
switch is ON.
y
OFF-LINE: The battery string is disconnected – circuit breaker/
switch is OFF.
y
OPTION STATUS – provides information for any installed option, such as the TRD VRLA Battery Thermal
Runaway Detection System
NO LIGHT:
No option is installed
GREEN LIGHT:
Option is installed and working normally
RED LIGHT:
Option is in alarm (for more information, refer to the installed option's manual)
y
EPO TRIPPED – Emergency Power Off input is active. This indicator is not persistent.
Figure 2. LED indicators
Figure 3. DCX LP unit
Figure 4. Mounting hardware kit
Figure 5. Electrical connection kit
3.1
3.1 Package Contents
Package Contents
Included with your product are the following items:
y
DCX LP unit (see Figure 3).
y
Mounting hardware kit with necessary screws and
washers (see Figure 4).
1 Left side rail
1 Right side rail
2 Bottom rail
4 1/2-13 x 2 1/2" hex-head screw
4 1/4-20 x 5/8" hex-head screw
4 1/4" split washer
4 1/4" flat washer
y
Electrical connection kit with necessary screws and
washers (see Figure 5).
1 3' Grounding cable - 1/4" holes, 1" center-to-center
2 Tie strap
12 3/8-16 x 1" hex-head screw
6 3/8-16 x 1" socket cap screw
4 6-32 x 3/8" Phillips
®
pan-head screw
18 3/8" flat washer
18 3/8" split washer
6 1/4-20 x 1 3/4" partial thread hex-head screw
12 1/4" Flat washer
6 1/2" Split lock washer
6 1/4-20 Hex nut
5 Screw finishing cap
2 Plastic termination plate shields
y
Termination bus plates with assembled isolators
y
Thermal Runaway Detection (TRD) kit
3.0
3.0 Unpacking and Inspection
Unpacking and Inspection
The DCX LP unit was carefully packaged at the factory to withstand the normal rigors of shipping. However, you should
carefully inspect the box and contents to confirm that no damage has occurred in transit. Most shipping carriers require
notification of shipping damage within twenty-four hours of delivery, and it is the responsibility of the recipient to inspect
the shipment immediately upon receipt. Remove the DCX LP unit and related hardware. Refer to Section 3.1 to confirm
that all parts are present for installation�