Measurememnts
Input
X
Power
actual active power on phase X [W]
App.Power
actual appartent power on phase X [VA]
Vrms
Effective voltage on phase X [V Rms]
Vrms ph-ph Effective line voltage on phase X [V Rms]
Vrms Bypass Effective bypass voltage on phase X [V Rms]
Irms
Effective current on phase X [A Rms]
Peak I Val.
Peak current on phase X [A]
Frequency
Frequency of the sinusoid voltage phase X [Hz]
Crest Factor Crest factor on phase X
Power factor Power factor on phase X
Note:
To change the phase X press the ENTER key.
Mearurements
Battery
Voltage
Voltage measured at the ends of the batteries [V]
Current
Current supplied by the batteries (negative if the batteries are being
charged) [A]
Residual Capac Battery charged status, expressed as a percentage [0-100%]
chg Status.
Status battery system
- Battery system standby (no charging)
- battery discharging
- end of autonomy
- Boost charge (charging phase 1)
- Charging (phase 2, current decreasing)
- Float charge
- Battery teste
- Equalization charge
- Battery broken
- max. charging time override
Tot autonomy Total autonomy the UPS would have with batteries charged 100%
Res. autonomy Residual autonomy of the UPS
End of aut V
Battery threshold voltage for end of autonomy
No, run down Total number of times the batteries have been completely run down
Use
Total number of hours the UPS has been running on battery
Cal.
Day and time the last calibration was made
No.Calibration Total number of calibrations made
Measurememts
Misc.
Int. Temp
Temperature inside the UPS [°C]
Pos.H.V.Bus
Voltage on the DC BUS positive [V]
Pos.H.V.Bud
Voltage on the DC BUS negative [V]