System Off command
From the “Command Panel” page, press the “System ON/OFF” icon to switch the System off.
Confirm “System OFF Command”, by selecting OK.
NOTE:
during prolonged periods of inactivity, it is good practice to shut down the UPS; open the input
and output switches (after system off) and lastly, with the UPS off, open the battery fuse holder
(SWBATT) to avoid unnecessary battery discharge.
When the UPS is started again, it is possible that date and time will need to be manually restored.
Power Off the UPS without access to the Display
Open SWOUT. The buzzer should start to inform the user that the output switch (SWOUT) is open and thus
the load is not supplied.
Open then SWBATT, SWIN and SWBYP if present.