Page
39
to
71
Configuring the UPS from display
Configurations which can be modified by the user from the display are listed in Table 2 (below).
FUNCTION
DESCRIPTION
DEFAULT POSSIBLE CONFIGURATIONS
ACCESS
LEVEL
Language
Selection of the mimic
panel language
English
English
Italian
German
French
Spanish
“PowerUser”
Homepage timeout
Selection of the screen
saver timeout
5 min.
1-240 minutes
“PowerUser”
Buzzer
Disables the alarm
buzzer
ON
OFF
ON
“PowerUser”
Date and time
UPS internal clock setup
-
-
“PowerUser”
Operating mode
Selection from among five
different operating modes ON LINE
ON LINE
ECO
FREQUENCY CONVERTER
SMART ACTIVE
STAND-BY OFF
“Expert”
Battery low
Estimated autonomy time
remaining for “battery
low” warning
3 min.
1-7 @ 1 min step
“Expert”
Auto Restart
Enables the auto restart
function
5 sec.
OFF
ON (configurable 0-240
seconds)
“Expert”
Auto Power Off
Enables and configures
the auto power off
function
OFF
OFF
ON (configurable 2-10%)
“Expert”
Output voltage
Selection of the output
voltage
(Phase - Neutral)
230V
220-240V (custom)
208V
200V
“Expert”
Output frequency
Selection of the inverter
frequency
50Hz
50Hz
60Hz
“Expert”
Automatic battery
test
Enables and schedules
the automatic battery test
40 h
OFF
ON (programmable)
“Expert”
User password
change
Replacement of the
current password with a
new one
-
Any combination of characters for a
maximum of 16
“User”
“PowerUser”
password change
Replacement of the
current password with a
new one
-
Any combination of characters for a
maximum of 16
“PowerUser”
“Expert” password
change
Replacement of the
current password with a
new one
Expert
Any combination of characters for a
maximum of 16
“Expert”
Table 2 – UPS configuration (available from display)