![background image](http://html1.mh-extra.com/html/alpha-outback-energy/spciiis-5000-48/spciiis-5000-48_user-manual_2905763066.webp)
64
WECO
Step 1. Use a custom-made RJ45 cable to connect inverter and Lithium battery.
Note
: connect the SPC-COMM cable in the RS-485 port of the battery
Note for parallel system:
1.
Only support common battery installation.
2.
Use one custom-made RJ45 cable (P/N: SPC-COMM) to connect any inverter (no need to connect to a
specific inverter) and Lithium battery.
Simply set battery type of this inverter to
“WEC” in LCD program 5
.
The remaining inverters are
set as “USE”.
Step 2. Switch on Lithium battery.
Step 3. Turn on the inverter.
Step 4. Be sure to select battery type as “WEC” in LCD program 5.
If communication between the inverter and battery is successful, the battery icon
on LCD display will
“flash”. Generally speaking, it will take longer than 1 minute to establish communication.