background image

User Manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPCIIIS-5000-48 

5kW with MPPT Solar Charger 

Inverter/Charger

 

 

 

 

 

 

                                                                                                                                                                                                                                 
 

 
 

 
 

 
 

 
 

 
 

 
 

 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 

 
 

 

                                                                                                                                                                                                                                Version: 1.3 

Summary of Contents for SPCIIIS-5000-48

Page 1: ...User Manual SPCIIIS 5000 48 5kW with MPPT Solar Charger Inverter Charger Version 1 3...

Page 2: ...cation 12 OPERATION 13 Power ON OFF 13 Operation and Display Panel 13 LCD Display Icons 14 LCD Setting 16 Display Setting 28 Operating Mode Description 34 Faults Reference Code 36 Warning Indicator 37...

Page 3: ...off the unit will not reduce this risk 5 CAUTION Only qualified personnel can install this device with battery 6 NEVER charge a frozen battery 7 For optimum operation of this inverter charger please f...

Page 4: ...ower from PV solar modules solar panels battery and the utility When MPP input voltage of PV modules is within acceptable range see specification for the details this inverter is able to generate powe...

Page 5: ...itch 7 AC input connectors 8 AC output connectors Load connection 9 PV connectors 10 Battery connectors 11 Circuit breaker 12 Current sharing port 13 Parallel communication port 14 Dry contact 15 USB...

Page 6: ...ews as shown below WARNING Make sure not to damage disconnect the cables that link the cover with the inverter case Mounting the Unit Consider the following points before selecting where to install Do...

Page 7: ...nt operation to use appropriate cable for battery connection To reduce risk of injury please use the proper recommended cable and terminal size as below Recommended battery cable and terminal size Typ...

Page 8: ...utility AC input is connected to IN and load AC to OUT and not the wrong way round and also that Line and Neutrals are connected correctly WARNING All wiring must be performed by a qualified personne...

Page 9: ...system safety and efficient operation to use appropriate cable for PV module connection To reduce risk of injury please use the proper recommended cable size as below Typical Amperage AWG no Section...

Page 10: ...10 mm for positive and negative conductors 2 Check correct polarity of connection cable from PV modules and PV input connectors Then connect positive pole of connection cable to positive pole of PV i...

Page 11: ...9 Final Assembly After connecting all wirings please put bottom cover back by screwing two screws as shown below...

Page 12: ...ull out the cable from the remote communication port Be sure to screw back the fixing plate to the inverter Step 2 Drill two holes in the marked locations with two screws as shown below chart Place th...

Page 13: ...install the monitoring software For the detailed software operation please check user manual of software inside of CD Bluetooth Connection This unit is equipped with a Bluetooth transmitter Download W...

Page 14: ...ttery or Solar Program 01 set as SUb or USb Battery voltage Low DC warning voltage Open Close Battery voltage Setting value in Program 13 or battery charging reaches floating stage Close Open Program...

Page 15: ...tus and input output power information LCD display Indicators LED Indicator Color Solid Flashing Messages Setting LED 1 Green Solid On Output powered by utility Setting LED 2 Green Solid On Output pow...

Page 16: ...charger current charger power battery voltage Configuration Program and Fault Information Indicates the setting programs Indicates the warning and fault codes Warning flashing with warning code Fault...

Page 17: ...l 1 975V cell 2 058V cell 2 058V cell Load Information Indicates overload Indicates the load level by 0 24 25 49 50 74 and 75 100 0 24 25 49 50 74 75 100 Mode Operation Information Indicates unit conn...

Page 18: ...If solar energy is not sufficient to power all connected loads utility power will supply power the loads with solar at the same time Battery energy provides power to the loads only when solar energy...

Page 19: ...ot be effected Saving mode enable If enabled the output of inverter will be off when connected load is pretty low or not detected 05 Battery type AGM Default Flooded User Defined If User Defined is se...

Page 20: ...ompatible to Lib protocol If selected programs of 02 26 27 and 29 will be automatically set up No need for further setting 3rd party Lithium battery If selected programs of 02 26 27 and 29 will be aut...

Page 21: ...11 Maximum utility charging current Note If setting value in program 02 is smaller than that in program in 11 the inverter will apply charging current from program 02 for utility charger 2A 10A 20A 3...

Page 22: ...at 5 of connected battery capacity 13 Setting voltage point back to battery mode when selecting SBU SBU priority or SUB solar first in program 01 Battery fully charged The setting range is from 48V to...

Page 23: ...tility will charge battery as first priority Solar energy will charge battery only when utility power is not available Solar and Utility Default Solar energy and utility will charge battery at the sam...

Page 24: ...s pressed for 1 minute Stay at latest screen If selected the display screen will not return to the default screen 20 Backlight control Backlight on Default Backlight off 22 Beeps while primary source...

Page 25: ...h click is 0 1V 28 AC output mode This setting can be changed only when the inverter is in standby mode Be sure that on off Switch is in OFF status Single This inverter is used in single phase applica...

Page 26: ...ization Battery equalization Battery equalization disable Default If Flooded or User Defined is selected in program 05 this program can be set up 34 Battery equalization voltage Default setting is 58...

Page 27: ...diately and LCD main page will shows If Disable is selected it will cancel equalization function until next activated equalization time arrives based on program 37 setting At this time will not be sho...

Page 28: ...Time setting Year For year setting the range is from 17 to 99 Functional Setting There are three function keys on the display panel to implement special functions such as USB OTG and timer setting fo...

Page 29: ...with your dealer or installer for detail instructions Export data log Press button to export data log from the inverter to USB disk If the selected function is ready LCD will display Press button to c...

Page 30: ...increment Press button to set up Solar Utility Timer Press button to select staring time Press or button to adjust values and press to confirm Press button to select end time Press or button to adjus...

Page 31: ...ut frequency Input frequency 50Hz PV voltage PV voltage 260V PV current PV current 2 5A PV power PV power 500W Charging current AC and PV charging current 50A PV charging current 50A AC charging curre...

Page 32: ...and PV charging power 500W PV charging power 500W AC charging power 500W Battery voltage and output voltage Battery voltage 50 0V output voltage 230V Output frequency Output frequency 50Hz Load percen...

Page 33: ...chart Load in Watt When load is lower than 1kW load in W will present xxxW like below chart When load is larger than 1kW 1kW load in W will present x xkW like below chart Battery voltage DC dischargin...

Page 34: ...erated this year and Load output energy this year PV energy generated this year energy 3 88MWh Load output energy this year 9 88MWh PV energy generated totally and Load output total energy Total PV en...

Page 35: ...33 Secondary CPU version Secondary CPU version 00001 23 Bluetooth version Bluetooth version 00001 03...

Page 36: ...oad is pretty low or not detected No output is supplied by the unit but it still can charge batteries Battery is charged by utility Battery is charged by PV energy Battery is charged by utility and PV...

Page 37: ...r energy and the utility will provide the loads Output power from utility Charger is available Power from utility Battery mode Output power from battery or PV Power from battery and PV energy PV energ...

Page 38: ...s detected by internal converter components 06 Output voltage is too high 07 Overload time out 08 Bus voltage is too high 09 Bus soft start failed 10 PV over current 11 PV over voltage 12 DCDC over cu...

Page 39: ...ver temperature None 03 Battery is over charged Beep once every second 04 Low battery Beep once every second 07 Overload Beep once every 0 5 second 10 Output power derating Beep twice every 3 seconds...

Page 40: ...LCD setting program 33 first Then you may apply this function in device by either one of following methods 1 Setting equalization interval in program 37 2 Active equalization immediately in program 3...

Page 41: ...n voltage point the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage If battery voltage is still lower than battery equalization vol...

Page 42: ...c Nominal Input Frequency 50Hz 60Hz Auto detection Low Loss Frequency 40 1Hz Low Loss Return Frequency 42 1Hz High Loss Frequency 65 1Hz High Loss Return Frequency 63 1Hz Output Short Circuit Protecti...

Page 43: ...50 load 10s 110 150 load Surge Capacity 2 rated power for 5 seconds Nominal DC Input Voltage 48Vdc Cold Start Voltage 46 0Vdc Low DC Warning Voltage load 20 44 0Vdc 20 load 50 42 8Vdc load 50 40 4Vdc...

Page 44: ...ant Current Absorption Constant Voltage Maintenance Floating Current Voltage T1 T1 10 T0 minimum 10mins maximum 8hrs T0 2 43Vdc 2 35Vdc 2 25Vdc Solar Input Rated Power 5000Wp Max PV Array Open Circuit...

Page 45: ...el numbers 9 Circulation Current under No Load Condition Max 2A Power Unbalance Ratio 5 100 Load Parallel communication CAN Transfer time in parallel mode Max 50ms Parallel Kit YES Note Parallel featu...

Page 46: ...to Utility first When the unit is turned on internal relay is switched on and off repeatedly LCD display and LEDs are flashing Battery is disconnected Check if battery wires are connected well Buzzer...

Page 47: ...with share current cable and parallel cable By default the inverter supports parallel operation Unless you re replacing the parallel card skip sections 2 3 otherwise install it according to the instru...

Page 48: ...G 6 mm2 1 2 1 6Nm You need to connect the cables of each inverter together Take the battery cables for example You need to use a connector or bus bar as a joint to connect the battery cables together...

Page 49: ...ts 8 units 9 units 80A 230VAC 120A 230VAC 160A 230VAC 200A 230VAC 240A 230VAC 280A 230VAC 320A 230VAC 360A 230VAC Note1 Also you can use 50A breaker for only 1 unit and install one breaker at its AC i...

Page 50: ...4 1 Parallel Operation in Single phase Two inverters in parallel Power Connection Load N L N L Communication Connection Three inverters in parallel Power Connection Load N L N L Communication Connecti...

Page 51: ...49 Four inverters in parallel Power Connection Load N L N L Communication Connection Five inverters in parallel Power Connection Load N L N L Communication Connection...

Page 52: ...50 Six inverters in parallel Power Connection Load N L N L Communication Connection Seven inverters in parallel Power Connection Load N L N L Communication Connection...

Page 53: ...N L N L Communication Connection Nine inverters in parallel Power Connection Load N L N L Communication Connection 4 2 Support 3 phase equipment Three inverters in each phase Power Connection Load N L...

Page 54: ...ter for the third phase Power Connection Load N L1 P1 P2 P3 L2 L3 N L1 L2 L3 Communication Connection Three inverters in one phase two inverters in second phase and two inverters for the third phase P...

Page 55: ...r for the other two phases Power Connection Load N L1 P1 P2 P3 L2 L3 N L1 L2 L3 Note It s up to customer s demand to pick 7 inverters on any phase P1 L1 phase P2 L2 phase P3 L3 phase Communication Con...

Page 56: ...r the other two phases Power Connection N L1 P1 P2 P3 L2 L3 N L1 L2 L3 Load Communication Connection Three inverters in one phase two inverters in second phase and one inverter for the third phase Pow...

Page 57: ...and only one inverter for the remaining two phases Power Connection N L1 P1 P2 P3 L2 L3 N L1 L2 L3 Load Communication Connection Two inverters in two phases and only one inverter for the remaining ph...

Page 58: ...o inverters in one phase and only one inverter for the remaining phases Power Connection N L1 P1 P2 P3 L2 L3 N L1 L2 L3 Load Communication Connection One inverter in each phase Power Connection N L1 P...

Page 59: ...e current sharing cable between the inverters which are in different phases Otherwise it may damage the inverters 5 PV Connection Please refer to user manual of single unit for PV Connection CAUTION E...

Page 60: ...lease select 3P1 in program 28 for the inverters connected to L1 phase 3P2 in program 28 for the inverters connected to L2 phase and 3P3 in program 28 for the inverters connected to L3 phase Be sure t...

Page 61: ...lowing order inverters However these inverters will automatically restart If detecting AC connection they will work normally LCD display in Master unit LCD display in Slave unit Step 5 If there is no...

Page 62: ...play in L3 phase unit Step 5 If there is no more fault alarm the system to support 3 phase equipment is completely installed Step 6 Please switch on all breakers of Line wires in load side This system...

Page 63: ...oss 83 The battery voltage of each inverter is not the same 1 Make sure all inverters share same groups of batteries together 2 Remove all loads and disconnect AC input and PV input Then check battery...

Page 64: ...4 on master battery first battery are to set up or change the group address NOTE 1 is upper position and 0 is bottom position Dip 1 Dip 2 Dip 3 Dip 4 Group address 1 RS485 baud rate 9600 Restart to t...

Page 65: ...for parallel system 1 Only support common battery installation 2 Use one custom made RJ45 cable P N SPC COMM to connect any inverter no need to connect to a specific inverter and Lithium battery Simp...

Page 66: ...erter no need to connect to a specific inverter and Lithium battery Simply set battery type of this inverter to WEC in LCD program 5 The remaining inverters are set as USE Step 2 Switch on Lithium bat...

Page 67: ...ter no need to connect to a specific inverter and Lithium battery Simply set battery type of this inverter to SOL in LCD program 5 The remaining inverters are set as USE Step 2 Open DC isolator and sw...

Page 68: ...inverter to BAK in LCD program 5 The remaining inverters are set as USE 3 Set the DIP address switches to ON OFF OFF OFF if it is a single battery If multiple batteries in parallel connect the RJ45 to...

Page 69: ...lable when the battery type is setting as Pylontech Battery WECO Battery Soltaro Battery or BAK Battery After battery is connected and communication signal is not detected for 3 minutes buzzer will be...

Page 70: ...GmbH reserves the right to make changes to the products and information contained in this document without notice Copyright 2020 Alpha and Outback Energy GmbH All Rights reserved For more information...

Reviews: