3.4  Protection 

Items

 

Description

 

Remark

 

Cell/PACK high-voltage 

When charging, the system will stop charging if any 

cell or PACK voltage reach the protection value and 

it will be released only when both Pack and cell 

voltage back to the release voltage range. 

Automatc 

recovery 

Cell/PACK low-voltage 

When discharging, it will reach over-discharged 

protection of battery to stop discharging if any cell or 

PACK voltage is under the protection value and it 

will be released only when all the cell voltage back to 

the release voltage range. 

Can Automatic 

recovery. Please 

charge timely, 

otherwise it may be 

in Low-power mode      

to be over-

discharged. 

High temperature 

When the battery cell, MOS, and ambient 

temperature are higher than the set value, the 

system will  stop  charging  or  discharging 

according  to  the category, or disconnect at the 

same time. 

Automatc 

recovery 

Low temperature 

When the battery cell, MOS, and ambient 

temperature are higher than the set value, the 

system will  stop  charging  or  discharging 

according  to  the category, or disconnect at the 

same time. 

Automatc 

recovery 

Charge overcurrent 

When the charging current is higher than the 

protection value, the system will stop charging. And 

it will release from the protection when the system 

delays after rated time. Please note the maximum 

charging current provided  by power supply should 

not exceed the protection value when using the 

battery. 

Automatic recovery. 

If            locked after three 

consecutive times, 

manual intervention 

is required. 

Overload 

When the discharging current is higher than the 

protection value, the system will stop discharging. 

And it will release from the protection when the 

system delays after rated time. Please note the 

maximum discharging current requested by the load 

should  not  exceed  the  protection  value  when 

using the battery. 

Automatic recovery. 

If  locked  after three 

consecutive times, 

manual intervention 

is required. 

Summary of Contents for AOESS48V-LFP4100

Page 1: ......

Page 2: ...l Terms Alpha and Outback Energy GmbH will retain the copyright of this document do not extract copy or translate in any ways without the written permission Disclaimer Please read this manual and spec...

Page 3: ...3 Protection 14 4 Installation and Usage 14 4 1 Installation preparation 14 4 1 1 Safety regulations 15 4 1 2 Environment requirement 16 4 1 1 Installation Tools 16 4 1 4 Safety Tips 16 4 2 Unpack 16...

Page 4: ...ct sunlight for a long time Do not allow the positive and negative connectors of the battery to connect the conductive objects atthe same time Electric shock risk Do not allow non technical personnel...

Page 5: ...d components otherwise the manufacturer will not be responsible for any damage caused by unauthorized disassembly or repair Do enable the battery to be safely grounded before use to make sure the syst...

Page 6: ...s please take these steps immediately Gas Inhalation Evacuate the people in the contaminated area and seek medical aid as soon as possible Eye Contact Flush your eye with clean and flowing water for 1...

Page 7: ...pact structure light weight and no pollution Built in BMS with the management functions to battery voltage current temperature and batteryhealth With LED display for SOC and operating status which is...

Page 8: ...id in case inverter allows that option If the photovoltaic solar energy is insufficient or at night it will automatically switch to the battery to deliver electric power to the load and when it run ou...

Page 9: ...Nominal Capacity Ah 100 0 Energy KWh 5 12 Width mm 442 0 2 Height mm 177 5 2 Depth mm 450 2 Weight kg 47kg 3 2 Interface definition See the interface description of AOESS48V LFP4100 series lithium bat...

Page 10: ...6 6 ALM Used to indicate the battery abnormality See Table 3 6 7 RUN Used to indicate the operating status of the battery See Table 3 6 8 Dial switch address Used to set the address bit of battery mod...

Page 11: ...6s and release it and the BMS will be reset the system restart Table 3 5 Dial switch address No Dial switch address RS485 CAN 1 2 3 4 5 6 0 OFF OFF OFF OFF OFF OFF Pack 0 Invalid 1 ON OFF OFF OFF OFF...

Page 12: ...ormal FLASH3 OFF According to battery state of charge Warning FLASH3 FLASH3 Under voltage OFF FLASH3 OFF OFF OFF OFF Stop charging Over current short circuit OFF ON OFF OFF OFF OFF Stop charging Tempe...

Page 13: ...ge 51 2V Charge voltage 56 0 57 6V Float charge voltage 54 4 55 2V Inverter Cut off voltage 48 0 51 2V BLVD 40 0 43 2V Nominal energy 5 12KWh Nominal capacity 100Ah Standard charge current 10A Max cha...

Page 14: ...same time Automatc recovery Low temperature When the battery cell MOS and ambient temperature are higher than the set value the systemwill stop charging or discharging according to the category or di...

Page 15: ...00 series lithium batteries Please read this manual and specs carefully before the installation be familiar with this equipment During the installation process please strictly follow the local safety...

Page 16: ...he insulation Completely isolated from water and no flammable or explosivematerials nearby 4 1 3 Installation Tools Installation Tools details Screwdriver slot cross Multi meter Wrench Clamp meters Di...

Page 17: ...Please record and feedback to the manufacturer if the inner packing is damaged after unpacking 4 2 2 Packing list One carton contains the items listed below please check carefully after unpacking PAC...

Page 18: ...f the bracket or cabinetmeets the weight requirements Check whether the power cable used meets the maximum current requirement for operation Check whether the overall layout of power supply equipment...

Page 19: ...he system breaker that connected the battery with inverter are disconnected 3 Turn on the signal switch of the battery observe whether there is alarms on the panel measure it with multi meter and reco...

Page 20: ...e double check the battery is in shut down and disconnect the circuit breaker unscrew the positive negative terminal bolts of the battery pack then connect the batteries to the positive negative busba...

Page 21: ...erter and open the setting menu then select Lib in the battery type and press the battery on switch to measure the battery voltage If normal output then turn on the battery to access breaker At the sa...

Page 22: ...from dormancy mode for charging normally if it can t be charged after 10 consecutive automatic wakeups it will no longer wake up automatically When the system is defined as charging ends the recovery...

Page 23: ...y according to the actual state of the battery or battery pack and observe whether the battery or battery pack is abnormal such as the voltagedifference of the battery at the end of charging and disch...

Page 24: ...rotection and try to release If the battery still can tbe turned on normallyafter above steps please contact Alpha and Outback Energy GmbH ALM always on Read the reason of the battery abnormality thro...

Page 25: ...battery CC CV 56 0V 50A and it will stop charging when the current 0 05C or reach the overcharged protection Charging standard When stop charging the voltage of battery is 54V or after charging for 8...

Page 26: ...User Manual revA_3521 Page 25 of 24...

Reviews: