Control unit

3

1

2

1 Control

2  Push up flap upstream of USB connection 

(for qualified personnel for software 

updates and for data logging)

3  Wall-mounted bracket

Underside of control

1

3

4

2

1  RBE (RS 485)

2  Network cable connection

3  LIN bus cable connection to the heat pump
4  not used

3.2  Accessories

The following accessories are available for the unit 

through the manufacturer's local partner:

 

 

Additional  masking  plate  for  the  front  cover 

panel, if the control is mounted on the wall

 

 

Domestic hot water tank

 

 

Changeover valve, domestic hot water

 

 

Room thermostat for switching the cooling 

function (if included)

 

 

Dew point monitor for protecting a system with 

cooling  function  at  low  flow  temperatures  (if 

available)

 

 

Expansion board for automatic changeover 

between heating and cooling mode (if available)

 

 

“Cooling package” for use of the cooling function

 

 

for units without cooling: Pump assemblies 

for  separate  storage  tank  and  in-line  tank 

integration (heating circuit)

 

 

Heating circuit safety package

 

 

Heat source circuit safety package

3.3  Function

Liquid refrigerant is evaporated (evaporator), the 

energy for this process is environmental heat and 

comes from the “ground” heat source (collector, 

borehole heat exchanger or groundwater via 

intermediate exchanger). The gaseous refrigerant 

is compressed (compressor), this causes the 

pressure to rise and therefore the temperature too. 

The gaseous refrigerant with high temperature is 

liquefied (condenser). 

Here the high temperature is discharged to the 

heating water and is used in the heating circuit. 

The liquid refrigerant with high pressure and high 

temperature is expanded (expansion valve). The 

pressure and temperature drop and the process 

begins again.
The heated heating water can be used for the 

domestic hot water charging or for the building 

heating. The temperatures required and use are 

controlled by the heat pump controller.
The integrated vibration isolators for the heating 

circuit and heat source prevent structure-borne 

sound and vibrations from being transferred onto the 

fixed pipes and therefore into the building.

Summary of Contents for SW 232H3

Page 1: ...UK 83057800cUK Translation into English of the original German operating manual Brine water heat pumps Operating Manual SW 232H3 SW 302H3...

Page 2: ...nstallation and connection 10 6 1 Dismantle the module box 10 6 2 Install the hydraulic connections 14 6 3 Connect the electrical cables 14 6 4 Installing the control 15 7 Flushing filling and venting...

Page 3: ...pump controller Operating manual of the expansion board accessories Logbook if included with this unit by the manufacturer Unit sticker The unit sticker contains important information for contact wit...

Page 4: ...personnel is able to carry out the work on the unit safety and correctly Interference by unqualified personnel can cause life threatening injuries and damage to property Ensure that the personnel is...

Page 5: ...k that the following damage and faults will occur Malfunctions and the failure of components e g pumps valves Internal and external leaks e g from heat exchangers Cross section reduction and blockages...

Page 6: ...ine circulation pump Rating plate Rating plates are attached to the following places on the unit on the right hand outer panel at the top on the rear panel at the top inside The rating plate contains...

Page 7: ...t cooling Pump assemblies for separate storage tank and in line tank integration heating circuit Heating circuit safety package Heat source circuit safety package 3 3 Function Liquid refrigerant is ev...

Page 8: ...flow temperature No unnecessarily high domestic hot water temperature note and follow local regulations Do not open windows with gap tilt open continuous ventilation but instead open wide for a short...

Page 9: ...allet truck alternatively with a handcart Transport with a pallet truck Transport the unit to the place of installation packaged and secured on a wooden pallet Unpacking NOTE If the unit is not transp...

Page 10: ...oom volume Refrigerant capacity kg Limit value kg m NOTE If several heat pumps of the same type are installed only one heat pump need to be taken into account If several heat pumps of different types...

Page 11: ...l of the module box 7 1 Remove the front panel of the module box on page 17 2 Close shut off valves to the heating circuit 3 Drain the unit via the filling and drain tap 1 of the heating 1 4 Close shu...

Page 12: ...riginal German operating manual ait deutschland GmbH 7 Remove the insulation on the hydraulic connec tions 8 Remove 4 clips on the hydraulic connections 9 Disconnect the hydraulic connections to do th...

Page 13: ...efully in the bottom of the housing and slowly and carefully push it in Lift up pipes so that they do not get damaged 2 Attach the two side retaining screws 3 Connect hydraulic connections At the same...

Page 14: ...heat source and the heating circuit 3 Recommendation Fit a dirt filter with mesh size 0 9 mm onto the heat source inlet 4 Ensure that the operating overpressures Technical data Scope of supply on page...

Page 15: ...unit 2 Plug the RJ 45 connector of the network cable into the socket of the control unit 1 1 NOTE The network cable can be retrofitted at any time 6 4 Installing the control NOTE The control can be in...

Page 16: ...lugs on the left and right 2 If visually unattractive Cut off the lugs on the rear of the control are only needed to insert in the front panel 3 Mark 2 drillholes Dimensioned drawing of control wall m...

Page 17: ...n promoting properties No formation of mineral scale Ideal for closed heating circuits ideal pH value due to self alkalinisation after filling the system If necessary simple alkalinisation to pH value...

Page 18: ...ssure of the safety valve is not exceeded 1 If installed Flush the domestic hot water charging circuit for approx 1 minute 2 Flush heating circuit thoroughly until no more air is discharged 3 Unscrew...

Page 19: ...customer service department In other countries Send completion report for heat pump systems and general checklist to the manufacturer s local partner 4 Arrange for the heat pump system to be started...

Page 20: ...isposal 12 1 Dismantling 9 9 Unit is safely disconnected from the power supply and protected against being switched back on again Collect all media safely Separate components by their materials 12 2 D...

Page 21: ...21 Subject to change without notice 83057800cUK Translation into English of the original German operating manual ait deutschland GmbH...

Page 22: ...it K hlung pK I Volumenstrom bar bar l h Druckverluste W rmepumpe p Volumenstrom bar l h 0 19 3900 Maximal zul ssiger Betriebsdruck bar 3 Allgemeine Ger tedaten Gewicht gesamt mit K hlung kg kg 207 Ge...

Page 23: ...source integrated yes no I Only compressor Follow local regulations Figures for 25 mono ethylene glycol 813572 813572 TechDat SW 232H3 813572 Datei 813572 TechDat SW 232H3 Heating capacity COP Name Pa...

Page 24: ...Druckverlustkurven SW 232H3 pWQ pWQ K Leistungsaufnahme Temperatur W rmequelle Druckverlust Heizkreis Druckverlust Heizkreis mit K hlung Volumenstrom W rmequelle Pe Heizleistung Maximalle freie Pressu...

Page 25: ...SW 262H3 Legende 823270 Coeffiicient of performance Leistungszahl Temperatur W rmequelle Druckverlust Heizkreis Druckverlust Heizkreis mit K hlung Volumenstrom W rmequelle Pe Heizleistung Maximalle f...

Page 26: ...2H3 Legende 823271 Coeffiicient of performance Leistungszahl Temperatur W rmequelle Druckverlust Heizkreis Druckverlust Heizkreis mit K hlung Volumenstrom W rmequelle Pe Heizleistung Maximalle freie P...

Page 27: ...meter 4 Heating water outlet flow 35 Outside diameter 5 Cable entry LIN bus cable 6 Cable entry 598 75 1 2 3 4 0 30 678 0 84 224 390 514 C 5 25 1500 6 535 745 589 C1 Legende D819462 Alle Ma e in mm A...

Page 28: ...nung Ma bild WZS 819447 Zust nderungstext PEP 015 2014 Datum 3 12 2014 JB Von Blatt von Werkstoff Gewicht Ma stab 1 5 Det Ma stab Datum Name Erstellt Gepr Norm 18 11 2014 Brueckner toleranz Allgemein...

Page 29: ...e DE819463 V1 Version 1 FS Freiraum f r Servicezwecke FZ Freiraum f r funktionsnotwendiges Zubeh r OKF Oberkante Fertigfussboden Alle Ma e in mm 3 2 1 A B C D E F Schutzvermerk ISO 16016 beachten Inst...

Page 30: ...DE819463 V2 Version 2 FS Freiraum f r Servicezwecke FZ Freiraum f r funktionsnotwendiges Zubeh r OKF Oberkante Fertigfussboden Alle Ma e in mm 4 3 2 1 A B C D E F Schutzvermerk ISO 16016 beachten Ins...

Page 31: ...GmbH 600 1 1 1575 OKF 950 1600 1000 1 FS V3 Legende DE819463 V3 Version 3 FS Freiraum f r Servicezwecke OKF Oberkante Fertigfussboden Alle Ma e in mm 4 3 2 1 A B C D E F Schutzvermerk ISO 16016 beacht...

Page 32: ...32 Subject to change without notice 83057800cUK Translation into English of the original German operating manual ait deutschland GmbH Hydraulic integration unit variant H heating...

Page 33: ...33 Subject to change without notice 83057800cUK Translation into English of the original German operating manual ait deutschland GmbH Hydraulic integration separate buffer tank...

Page 34: ...mestic hot water ZWE 28 Brine circulation pump VBO Additional circuit board 29 Dirt trap max 0 6 mm screen size 15 Mixing circuit three way mixer MK2 3 discharging 30 Collection container for brine mi...

Page 35: ...xing circuit 1 Charge discharge cooling mixer 1 closed Charge discharge cooling mixer 1 open Auxiliary circulation pump Heating circuit circulating pump Diverting valve for domestic hot water Brine pr...

Page 36: ...y if phase sequence in the order of 11 14 is closed Compressor Contactor for compressor 1 Starting current limit Power supply compressor right hand rot field is mandatory Compressor output control con...

Page 37: ...compressor 1 Resistor Terminal in switch box heat pump Control connector Plug 230V Pump Plug PWM Energy supplier contact closed on release bridge if no blocking interval 817421a K40 4 64kOhm X1 X2 Q1...

Page 38: ...ding resistor Sensor card connector 817421a XJ5 R4 XJ7 R8 23kW 14 7kOhm 26kW 15 4kOhm 30kW 16 2kOhm X9 R6 R7 B10 X11 XJ15 B11 XJ16 K22 X6 XJ13 X13 K11 1 2 3 4 5 6 7 8 1 2 8 A B C D E F A B C D E F Bla...

Page 39: ...ie Service GmbH Nr 0036 UK818173c Company Place date Signature EN 60335 1 2 40 EN ISO 13857 Unit model 10070141 Module EN 378 Pressure equipment component Category SW 42H3 SW 62H3 SW 82H3 SW 102H3 Des...

Page 40: ...ait deutschland GmbH Industriestra e 3 D 95359 Kasendorf E info alpha innotec de W www alpha innotec de alpha innotec an ait deutschland GmbH brand UK...

Reviews: