31
Subject to change without notice | 83061600bUK | ait-deutschland GmbH
≥200
≥800
≥800
≥1000
9
>2100
<300
1020
0
+20
1780
1210
KA
OKF
> 2965
>
2350
FWS
1020
0
+20
795
1050
B2
B1
5
3
5
1
1
2
FA
FA
≥150
G
7
6
1
V1
BS
LRR
LRL
8
7
6
5
4
3
2
1
www.alpha-innotec.de
D - 95359 Kasendorf
Industriestraße 3
Alpha-InnoTec GmbH
Schutzvermerk nach DIN 34 beachten
1
4
Ers. d.
Ers. f.
A
B
C
D
E
F
F
E
D
C
B
A
4
3
2
1
Benennung
Aufstellungsplan
819336
b
a
-
Zust. Änderungstext
PEP 032/2009
PEP 024/2010
PEP 032/2009
Datum
25.1.2010
16.6.2010
25.10.2010
DH
Von
DH
RA
Blatt
von
Werkstoff
Gewicht
Maßstab
1:35
1:40
Det. Maßstab
Datum
Name
Erstellt
Gepr.
Norm.
21.1.2010 Haderdauer
25.10.2010 Aepfelbach
toleranz
Allgemein-
DIN ISO 2768 -c
Oberflächen
ArtikelNr.
LW 140, LW 140L, LW180, LW 180L, LW180H
Keys: UK819336b-1
All dimensions in mm.
V1
Version 1
OKF
Finished floor level
FA
Finished external façade
LR
Air direction
LRR
Air direction of units with fan right-hand side
LRL
Air direction of units with fan left-hand side
BS
Operating side
FWS
Finished wall thickness
KA
Condensate drain
G
Detail of installation in the light well
Tipping dimension of the heat pump = 2050
Pos. Name
Dim.
B1
If finished wall thickness 240 to 320
2340
If finished wall thickness 320 to 400
2260
B2
If finished wall thickness 240 to 320
920
If finished wall thickness 320 to 400
840
1
Accessories: Wall duct 1000x1000x420
2
Accessories: Air duct 900x900x1000
3
Accessories: Air duct bend 900x1050x1450
5
Installation above ground level
Accessories: Weather louvre 1045x1050
6
Installation in the light well
Accessories: Rain louvre 1045x1050
7
Provided on site by the customer: Light well with water
outlet
min. free cross-section 0.75m²
9
Minimum clearance for service purposes
If clearances are reduced to the minimum dimension the air
ducts must be shortened. This causes a substantial
increase in the sound pressure level!
Installation plan Version 1
LW 161H(L)/V
Summary of Contents for LW 161H/V
Page 1: ...UK 83061600bUK Air Water Heat Pumps Indoor installation Operating Manual LW 161H L V...
Page 36: ...36 Subject to change without notice 83061600bUK ait deutschland GmbH Row tank LW 161H L V...
Page 44: ...44 Subject to change without notice 83061600bUK ait deutschland GmbH...
Page 45: ...45 Subject to change without notice 83061600bUK ait deutschland GmbH...
Page 46: ...46 Subject to change without notice 83061600bUK ait deutschland GmbH...
Page 47: ...47 Subject to change without notice 83061600bUK ait deutschland GmbH...