Emergency mode

The emergency mode provides heating operation and domestic 

hot water preparation as well as the frost protection function and 

the screed heating program even if, after switching on the con-

troller voltage

 

one or more basic system components were not detected 

during the self test,

 

however, at least the system components required for the 

emergency mode were detected during the self test.

The emergency mode is activated automatically.
A connection error is first displayed on the screen of the heating 

and heat pump controller. 
Im Bildschirm des Heizungs- und Wärmepumpenreglers wird zu-

nächst ein Kommunikationsfehler ausgegeben. 

Example of a connection error displayed on the screen. 
Beispiel eines im Bildschirm angezeigten Kommunika-
tionsfehlers

The navigation screen is displayed by turning the “rotary push-

button”. 
If the emergency mode is active, corresponding warning symbols 

are shown in the standard screen. 

During the emergency mode, the compressor request is locked. 

To ensure heating operation and domestic hot water preparation, 

set the “2nd heat gen.” option as the “Heating” operating mode 

and the “Domestic hot water” operating mode. 
During the emergency mode, the search for missing system com-

ponents continues in the background.

If the missing components are detected during the emergency 

mode, the system is automatically restarted.

The setting of the operating modes “Heating” and “Domestic hot 

water” must be manually reset to “Auto(matic)”.

Summary of Contents for Luxtronik Series

Page 1: ...HMD 2 Controller part 2 Scope of delivery Montage Electrical connections Software update Commissioning Switching on for the first time Addressed heat pump Program area Cooling Program area Service App...

Page 2: ...parts confiden tially The information contained herein is protected by copyright No part of this information may be reproduced transmitted cop ied stored in electronic data systems or translated into...

Page 3: ...stallation 39 Outputs 39 Inputs 39 Connections 39 Interfaces 39 Protection class 39 Temperature sensor characteristic curve 39 Sensor measuring range 40 SYSTEM SETTING DURING COMMISSIONING 41 ABBREVIA...

Page 4: ...on the control board are assigned by the terminal diagram of the hydraulic module In addi tion you will find the assignment on the switchbox cover Scope of delivery Heating and heat pump regulator co...

Page 5: ...drill them into the fixing point Insert dowels and screw the housing of the external sensor to the wall NOTE Dowels and screws for fastening the external sensor are not included in the scope of suppl...

Page 6: ...downgrades can be carried out via the USB in terface on the control unit of the heating and heat pump control ler 1 Expose the USB interface on the control unit Part 1 of the controller manual program...

Page 7: ...enu item Reset Startup Parameters appears on the dis play instead of the Startup guide menu item Switching on Commissioning When switching on the controller voltage or after a restart of the heating a...

Page 8: ...e continues with further input prompts which concern the settings of your system for example with Further queries will follow The startup guide leads you step by step through several selec tion option...

Page 9: ...gs made during commissioning startup guide This al lows you to quickly and easily reset the system to the status it had at startup The data is stored on the circuit board of the control unit Follow th...

Page 10: ...s Heizungs und W rmepumpenreglers wird zu n chst ein Kommunikationsfehler ausgegeben Example of a connection error displayed on the screen Beispiel eines im Bildschirm angezeigten Kommunika tionsfehle...

Page 11: ...hat heat pump 2 is currently ad dressed in the system s Service area If you want to call up information for the heat pump currently dis played 1 or 2 in the system area Service or want to make set tin...

Page 12: ...ling The Cooling function with automatic changeover between heating mode and cooling mode depending on requirements can be used with reversible LWD heat pumps and one mixing cir cuit In order to use t...

Page 13: ...e only during the summer months or shut off the cooling during the heating period by means of a room thermostat Otherwise it is possible that depending on the location of the outdoor sensor the system...

Page 14: ...TIVE COOLING NOTE The active cooling function can only be used if the system is utilised in accordance with the corresponding hydraulic diagram There is otherwise no guarantee that the active cooling...

Page 15: ...perature Intake compressor Compressor intake temperature Intake vapor Evaporator intake temperature Comp Heater Compressor heating temperature Superheat Superheating temperature Targeted Superheat Sup...

Page 16: ...pening EEV heating Electronic expansion valve heating EEV cooling Electronic expansion valve cooling Undercooling EEV Calculated under cooling at the electronic expansion valve THG Grenze Maximum hot...

Page 17: ...hours domestic hot water Operation hours cool Operation hours Cooling NOTE The compressors are only energised alternately follow ing the impulses A variation in the operation hours of the compressors...

Page 18: ...eating DHW Defrost El Sup bl Software version RBE Software version of the room control unit RBE Defrost demand Defrosting requirement in Last defrost Time of last defrost Query error memory NOTE If 2...

Page 19: ...e mixing circuit 1 Targ service water Set point temperature domestic hot water preparation target value max Highest requirement setpoint from the Smart system UFH total HC Number of floor heating circ...

Page 20: ...ntroller maunual program area Service sec tion Data logger Cur room temp HC Current room temperature of the worst room in the heating circuit Targ room temp HC Target temperature of the worst room in...

Page 21: ...Set the first digit by turning the turn push button and confirm the entry by pressing the button Move to the respective next entry field and repeat the steps described above Finally move to and save t...

Page 22: ...at pump is set at an outside temperature of 20 C For further details see point min AT flow max and the following diagrams VL AT 20 C min AT Flow max Flow max low limit of applic Hysteresis HR setting...

Page 23: ...tr Hysteresis cooling circuit Standard value for reversible air water heat pumps 3 K service water max Maximum domestic hot water temperature A value which is set to limit the maximum set temperature...

Page 24: ...paration energises but only if this has been released previously in the heating mode Defr cycle max Defrost cycle time maximum time between two defrost processes You can find the time to be set for th...

Page 25: ...d on No Remote maintenance function switched off part 1 of the controller manual program area Service sec tion Remote maintenance Yes Setting only effective with an outdoor temperature 0 C Heating cir...

Page 26: ...ssor stage cuts in If the difference between the return flow set and actual values is greater than the setting Hysteresis 2 CP short then the second compressor stage cuts in after this time NOTE A com...

Page 27: ...eating and floor heating circulating pump suppl pump additional circulating pump DHW pump Domestic hot water circulation pump fan heats pump Fan well or brine circulation pump MC open 1 Mixer 1 OPEN M...

Page 28: ...ring this scrolling Efficiency pump The menu is not shown in full here Heat distrib sys Heat distribution system radiator Radiator s floor heat Floor heating control heating Control of the heating cir...

Page 29: ...water Position Tank Integrated in the heat generator heat pump or associated hydraulic component Integrated Integrated directly in or on the heating or hot water storage tank no ZWE 1 connected Outle...

Page 30: ...s applies Heating The heat pump operates in the setpoint value range plus increase heating HR heating hysteresis in heating mode NOTE Higher increases in temperatures can lead to loss of comfort in Sm...

Page 31: ...B C D E F 3 AIT ait deutschland GmbH L1 L1 L1 L 2 2 IN1 IN2 IN3 A1 A2 A1 A2 IN4 IN5 A3 A1 nderung Datum Datum Bearbeiter Gepr ft Norm Name 09 10 2015 Pfleger R LWD LWD R SELECTING LANGUAGE OF THE SCRE...

Page 32: ...the current tem perature setpoint of the screed heating program at the respective flow sensor by opening or closing the mixing circuit valve The mixing circuit control and temperatures have no influen...

Page 33: ...sary for the screed heating phase to integrate additional heat gen erators in the system The menu is not shown in full here scroll down the screen Answer the confirmation prompt NOTE If you respond to...

Page 34: ...se is switched off this must be set in the menu Mode of operation Deselect program area not required The example shown reveals that the menus of the pro gram area Heating are displayed in the screen T...

Page 35: ...l temperature sensor plug and connection line 712 Domestic hot water sensor Please call fitter Break or short circuit in the domestic hot water sensor No fault shutdown Check domestic hot water sensor...

Page 36: ...nsor External energy source Check sensor External energy source plug and connection line 736 Error solar collector Please call fitter Only possible with installed expansion board Break or short circui...

Page 37: ...781 Liquid temp sensor before EXV Liquid temperature sensor upstream of the ex valve is defective Check the sensor connector and connection cable 782 Suction gas EVI temp sensor Suction gas EVI temper...

Page 38: ...operation after 2 hours If the shutdown occurs 5 times within 24 hours error 800 is written to the fault memory Remove energy from desuperheater memory The machine can be restarted as soon as the temp...

Page 39: ...quickly Technical Data INSTALLATION Only in frost free dry and weatherproof rooms Ambient temperature 0 C 35 C Electrical connection 230 V AC 18 VA 0 1 A max power consumption regulator without any a...

Page 40: ...sor Measuring range Autom value in case of sensor defect PEX 40 C to 40 C TA 50 C to 90 C 5 C TBW 45 C to 155 C 75 C TFB1 20 C to 150 C 75 C TRL ext 40 C to 40 C 5 C TVL 0 C to 100 C 5 C TVL2 TEH 0 C...

Page 41: ...turn 50 C C 35 C 70 C 1 Fitter Hysteresis HC 2 0 K K 0 5 K 6 0 K 0 5 Fitter hysteres SW 2 0 K K 1 0 K 30 0 K 1 Fitter RT incr max 7 0 K K 1 0 K 10 0 K 1 AS Release 2 CP 5 C C 20 C 30 C 1 Fitter Releas...

Page 42: ...ixed Tp Analog In Fitter setting mc1 Set AT Set AT Fixed Tp Fitter Cooling Fixed Tp Set AT Fixed Tp User screed heating w mixer wo mixer w mixer User El Anode device dependent No Yes AS Heating limit...

Page 43: ...SW Heating Fitter Position Integrated Integrated Tank Fitter Outlet installation dependent output contact Fitter Second heat gen 2 Type No No El Rod Fitter Function No No Heating SW Fitter Position T...

Page 44: ...LWAV Performance controlled Air Water heat pump outdoor LWC Air Water Compact heat pump LWCV Performance controlled Air Water Compact heat pump LWD Air Water heat pump Dual Abbreviation Meaning LWDV...

Page 45: ...estic hot water UFH Floor heating circuit UWP Circulation pump VBO Fan well or brine circulation pump VD Compressor W W Water water heat pump WP Heat pump WW Domestic hot water WWC Water water Compact...

Page 46: ...46 We reserve the right to make technical changes 83055600dUK Translation of the original instruction manual HMD 2 ait deutschland GmbH...

Page 47: ...47 We reserve the right to make technical changes 83055600dUK Translation of the original instruction manual HMD 2 ait deutschland GmbH...

Page 48: ...ait deutschland GmbH Industriestra e 3 D 95359 Kasendorf E info alpha innotec de W www alpha innotec de alpha innotec an ait deutschland GmbH brand UK...

Reviews: