RC3-LOG & RC3P-LOG INSTRUCTION MANUAL 

 

 

Page 

10

 

 

SHAWALMEX-EUROPE BV

 

 

 RC3-LOG & RC3P-LOG INSTRUCTION MANUAL SEPT 2018 

 
 

 

 

Another option for changing the setpoints of the platens is by using the Control loop screens (figure 8) 
 

 

Once the desired platen control loop screen is selected, push the scroll button

2 times and the temperature 

will become black. By using the raise/lower buttons 

the temperature value can be set to the desired 

value. 

 

Once the desired value has been reached push the scroll button

 once more to enter the new value. Pushing 

the page button will lock the new temperature value: 

 

Important:

 The maximum recommended operating temperature is 325

F (163

C). 

5.1.3.  Setting the dwelltime 

Push the page button 

 untill the Process overview screen (Figure 5) is shown. Push the scroll button 

 

and the raise/lower buttons 

to scroll to dwelltime. Once the dwelltime is selected pushing the scroll 

button will activate the black up/down arrows   and the dwelltime can be changed with the raise/lower buttons 

 

Summary of Contents for RC3-LOG

Page 1: ...ATALOGGING TEMPERATURE CONTROL PANEL This manual was prepared to present the correct methods and procedures of operating and maintaining your ALMEX TEMPERATURE CONTROL PANEL Read this manual carefully...

Page 2: ...Platen Temperature 7 5 1 2 Protecting Temperature Controller Settings 5 2 1 Set the Timer 10 5 3 Heating the Vulcanizer 11 5 3 1 Manual Heating 12 5 4 Temperature Control 12 6 MAINTENANCE 12 6 1 Open...

Page 3: ...RC3P LOG Serial Number Weight 15 kg Voltage 380 420 volt Phase 3 Cycle Hertz 50 60 Amperage Maximum Per Platen 16 Amp Total 32 Amp Circuit Overcurrent Protection Required 32 Amp Temperature Sensor 100...

Page 4: ...LOG Year of Construction 2018 has been manufactured using the following transposed harmonized European Standards EN 60204 1 Safety EN 50081 1 Emissions EN55011 EN 50082 1 Immunity EN61000 4 2 3 4 5 a...

Page 5: ...mperature control panel 2 All of the electrical components contain live circuits Do not open or service any of the electrical equipment without disconnecting the main power supply 3 Incorrect voltage...

Page 6: ...T 2018 4 ASSEMBLY 4 1 Unpacking Carefully unpack temperature control panel from the box and inspect for damage Any damages or shortages should be reported to the carrier and or SHAW ALMEX EUROPE BV 4...

Page 7: ...ure set points for top and bottom platen The temperature controller has many other settings that have been set by the factory The operator interface consists of a display screen and four navigation pu...

Page 8: ...in many cases allowing the user to select one from a number of alternative values within menu items Theses keys are also used to navigate through the virtual keyboards and number pads used to enter te...

Page 9: ...Platen Temperatures Push the page button untill the Process overview screen Figure 5 is shown Push the scroll button and the raise lower buttons to select the setpoint or dwelltime that needs to be c...

Page 10: ...can be set to the desired value Once the desired value has been reached push the scroll button once more to enter the new value Pushing the page button will lock the new temperature value Important Th...

Page 11: ...sq cm before heating 3 Press the blue TIMER RESET button at the timer Setting the A M button to A will start the heat cycle 4 Turn the A M switch to the A on automatic position to begin heating the vu...

Page 12: ...otherwise excessive temperatures will occur 3 The parameters can be adjusted so that set point is reached in the fastest possible time straight line heating but this will cause the temperature to ove...

Page 13: ...calibration unless the controller the heating element or the temperature sensor is changed Refer to the special autotuning instructions for autotuning your RC3 P log controller 7 TROUBLESHOOTING This...

Page 14: ...iving incoming power and is receiving a signal from the controller but is not sending outgoing power then that relay is faulty and must be replaced 7 Loose connection in cable or platen connector 7 Re...

Page 15: ...ture controller 2 Refer to ALMEX NANODAC instruction manual Replace temperature controller 8 Service 8 1 Emergency Service Contact Service Department Telephone 31 652 667 301 Fax 31 842 202 967 Mail S...