Publication 1757-RM810A-EN-P - May 2002
3-32
Functional Blocks
Output Ranges
•
CVEUHI and CVEULO define the full range of CV in engineering units. If this block has a secondary, it brings the
secondary’s input range through the BACKCALC and sets its CV range to that. If it has no secondary, CVEUHI and
CVEULO track its own input range (XEUHI and XEULO).
•
OPHILM and OPLOLM define the normal high and low limits for OP as a percent of CV range; these are
user-specified values. OP clamps to these limits if algorithm’s calculated result (CV) exceeds them or another
function block or user program attempts to store an OP value that exceeds them. However, an operator may store
an OP value that is outside these limits.
•
OPEXHILM and OPEXLOLM define the extended high and low limits for OP as a percent of the CV range. These are
user-specified values. Operator is prevented from storing an OP that exceeds these limits.
Parameters
ALMDB
ALMDBU
ALMTM
ARWNET [1..8]
ARWOP
ASTEPID
BADCTLALM.FL
BADCTLALM.PR
BADCTLALM.SV
BADCTLFL
BADCTLOPT
CTLINIT
CV
CVEUHI
CVEULO
DESC
ESWENB
ESWFL.AUTO
ESWFL.BCAS
ESWFL.CAS
ESWFL.MAN
ESWPERM
EUDESC
FBORSTS
GAINHILM
GAINLOLM
HIALM
HIALM.PR
HIALM.SV
HIALM.TYPE
HOLDOPT
HOLDRATE
HOLDVAL
INALM
INITMAN
INITREQ [1..8]
INITVAL [1..8]
K
LASTMODEREQ
LASTOPREQ
LASTOPTYPE
LASTREQFL
LASTSTEP
MODE
MODEAPPL [1..4]
MODEATTR
MODEATTRFL.NORM
MODEATTRFL.OPER
MODEATTRFL.PROG
MODEFL.AUTO
MODEFL.BCAS
MODEFL.CAS
MODEFL.MAN
MODEFL.NORM
MODEPERM
MODEREQ
MODETRACK
NORMMODE
NORMMODEATTR
NUMONESHOT
NUMPRI
NUMPROPREQ
NUMSEC
OP
OPBIAS
OPBIAS.FIX
OPBIAS.FLOAT
OPBIAS.RATE
OPEU
OPEXHIFL
OPEXHILM
OPEXLOFL
OPEXLOLM
OPHIALM.DB
OPHIALM.DBU
OPHIALM.FL
OPHIALM.PR
OPHIALM.SV
OPHIALM.TM
OPHIALM.TP
OPHIFL
OPHILM
OPLOALM.DB
OPLOALM.DBU
OPLOALM.FL
OPLOALM.PR
OPLOALM.SV
OPLOALM.TM
OPLOALM.TP
OPLOFL
OPLOLM
OPMINCHG
OPREQ
OPROCLM
OPROCNEGFL
OPROCPOSFL
OPSECDATA.ARWSTS
OPSECDATA.EUHI
OPSECDATA.EULO
OPSECDATA.INITREQ
OPSECDATA.INITVAL
OPSECDATA.ONESHOT
OPSECDATA.ORFBVA
OPSECDATA.OROFFS
OPTYPE
ORDERINCM
REDTAG
RESTARTOPT
SAFEOP
SECINITOPT [1..8]
SIALM.FL
SIALM.OPT
SIALM.PR
SIALM.SV
SIFL
SIOPT
SPHILM
STARTOPT
STARTRATE
STARTVAL
STOPOPT
STOPRATE
STOPVAL
TMOUTFL
TMOUTMODE
TMOUTTIME
X1
X1P
X1STS
XEUHI
XEULO
Summary of Contents for ProcessLogix 1756-IA16
Page 1: ...ProcessLogix Function Blocks 1757 Series Reference Manual Spare Allen Bradley Parts...
Page 2: ......
Page 40: ...Publication 1757 RM810A EN P May 2002 2 20 Physical Equipment Blocks...
Page 116: ...Publication 1757 RM810A EN P May 2002 3 76 Functional Blocks...
Page 119: ...Spare Allen Bradley Parts...