Publication 1757-RM810A-EN-P - May 2002
Functional Blocks
3-11
AOCHANNEL
DICHANNEL
Description
Provides a standard analog output signal for operating final control elements.
Function
•
Brings OP data from connected blocks and conveys OP data to be stored in an associated IOM block.
•
Sets INITVAL parameter to appropriate value based on echo data.
•
Assigns safe value if STS parameter is BAD or UNCERTAIN.
•
Sets INITREQ to TRUE value if AOC or IOM block is inactive or a communications error occurs.
Inputs
Only one control block can interface to this block.
Outputs
Floating point value in engineering units.
Associated
Block
Prior to loading, block must be “associated” with 1 channel of corresponding IOM block that interfaces with physical
AO hardware module at execution runtime.
Parameters
BACKCALCOUT
BADCAL
BADCODE
CALBIAS
COMMFAILFL
DEBUG
EXECCOUNT
FETCHMODE
FREEZETIME
IOCNUMBER
INITREQ
INITVAL
IOCSTATE
IOCTYPE
IOMCONN
OP
OPFINAL
OPSOURCE
ORDERINCM
UPDATOPT
Description
Provides a standard digital interface to control blocks.
Function
•
Brings PV data from an associated IOM block.
•
Assigns Bad status to PV parameter when appropriate
Inputs
Digital (PV) signals received from the field.
Outputs
PV status value that can be used by other data points in system.
Associated
Block
Prior to loading, block must be “associated” with 1 channel of corresponding IOM block that interfaces with physical
Digital Input hardware module at execution runtime.
Parameters
BADCODE
BADPV
COMMFAILFL
COS
DEBUG
EXECCOUNT
FETCHMODE
FREEZETIME
HWFAULT
INBADOPT
IOCNUMBER
IOCSTATE
IOCTYPE
IOMCONN
NOFIELDPWR
ORDERINCM
PVFL
PVSTS
PVVAL
PVVALSTS
UPDATOPT
WIREOFF
Summary of Contents for ProcessLogix 1756-IA16
Page 1: ...ProcessLogix Function Blocks 1757 Series Reference Manual Spare Allen Bradley Parts...
Page 2: ......
Page 40: ...Publication 1757 RM810A EN P May 2002 2 20 Physical Equipment Blocks...
Page 116: ...Publication 1757 RM810A EN P May 2002 3 76 Functional Blocks...