Publication 1757-RM810A-EN-P - May 2002
Functional Blocks
3-7
TOTALIZER
Description
Periodically adds an input value (P1) to an accumulator value (PV); sets status flags to indicate when accumulator
value is “near”, “nearer”, “nearest” the user specified target value.
Function
Typically used to accumulate flows. For situations where flow transmitter may not be precisely calibrated near
zero-flow value, a zero-flow cutoff feature is provided such that when P1 is below the cutoff value it clamps to 0
(zero).
Block also supports warm restart.
Input
One input (P1) is required:
•
P1 is the value to be accumulated -- input value may be real, integer or Boolean, but is stored as a real number.
•
P1 must be fetched from another block.
•
Number of process input connections is 1.
Outputs
The following outputs are produced:
•
Accumulated value (PV) and its status (PVSTS), as well as a Boolean flag, PVSTSFL.BAD, to indicate to other
function blocks, that this block’s PV status is bad.
•
Flags, indicating if accumulated value has reached user-specified target value or one of the accumulator deviation
trip points (ACCTVFL and ACCDEV.FL(1-4]).
Equations
You can configure PVEQN to specify how the block should handle bad input and warm restarts. Specific handling
combinations for a given PVEQN selection are:
Equation
Bad Input Handling
Warm Restart Handling
EqA
Stop accumulation while input is bad
Continue after input turns valid
EqB
Use last good value if input is bad
Continue after input turns valid
EqC
Stop if the input is bad and set PV to NaN
Continue after input turns valid
EqD
Stop accumulation while input is bad
Stop after a warm restart
EqE
Use last good value if input is bad
Stop after a warm restart
EqF
Stop if the input is bad and set PV to NaN
Stop after a warm restart
Parameters
ACCDEV.FL [1..4]
ACCDEV.TP [1..4]
ACCTV
ACCTVFL
CI
CMDATTR
COMMAND
CUTOFF.LM
DELTATIME
DESC
LASTGOOD
OLDAV
ORDERINCM
P1
P1STS
PV
PVEQN
PVFORMAT
PVSTS
PVSTSFL.BAD
PVSTSFL.MAN
PVSTSFL.NORM
PVSTSFL.UNCER
PVVALSTS
RESETFL
RESETVAL
STARTFL
STATE
STOPFL
TIMEBASE
Summary of Contents for ProcessLogix 1756-IA16
Page 1: ...ProcessLogix Function Blocks 1757 Series Reference Manual Spare Allen Bradley Parts...
Page 2: ......
Page 40: ...Publication 1757 RM810A EN P May 2002 2 20 Physical Equipment Blocks...
Page 116: ...Publication 1757 RM810A EN P May 2002 3 76 Functional Blocks...
Page 119: ...Spare Allen Bradley Parts...