Publication 1757-RM810A-EN-P - May 2002
3-24
Functional Blocks
nOON (n out of N voting)
NOR
Description
n-out-of-N voting block; outputs are computed as follows:
•
VOTED output is set to ON if at least n inputs are ON, otherwise it is set to OFF.
•
ORED output is set to ON if any input is ON, otherwise it is set to OFF.
•
ALARM output is a pulse output -- every time an input turns ON, a fixed pulse (of the pulsewidth specified by
PULSEWIDTH parameter) is generated, provided the total number of inputs which are ON is less than n.
Function
Provides VOTED, ORED and ALARM outputs in support of logical functions.
Inputs
IN [1..20] = Boolean value
n = 8-bit unsigned integer (range = 1-5)
There can be a maximum of 20 inputs (N = 20)
Outputs
VOTED, ORED = Boolean state (ON or OFF) as determined by the inputs.
ALARM = pulse output, width specified by parameter PULSEWIDTH. PULSEWIDTH is a unit integer with time unit in
seconds
Parameters
ALARM
IN [1..20]
N
ORDERINCM
ORED
PULSEWIDTH
VOTED
Description
Provides an up to 8-input NOR algorithm, meaning that it performs an inverted OR function. Each input
(IN [1], IN [2], ..., IN [8]) has the capability of being optionally inverted, if required.
Function
Turns the digital output (OUT) OFF if any one input (IN [1], IN [2], ..., IN [8]) is ON; therefore:
If all inputs are OFF, then: OUT = ON.
If any one input is ON, then: OUT = OFF.
Truth Table
IN [1]
OFF
OFF
ON
ON
IN [2]
OFF
ON
OFF
ON
Inputs
IN [1..8] = Boolean values
Outputs
OUT = Boolean value controlled by status of input signals
Parameters
INPTINVSTS [1..8]
Summary of Contents for ProcessLogix 1756-IA16
Page 1: ...ProcessLogix Function Blocks 1757 Series Reference Manual Spare Allen Bradley Parts...
Page 2: ......
Page 40: ...Publication 1757 RM810A EN P May 2002 2 20 Physical Equipment Blocks...
Page 116: ...Publication 1757 RM810A EN P May 2002 3 76 Functional Blocks...
Page 119: ...Spare Allen Bradley Parts...