3-26
Functional Blocks
OR
PULSE
Description
Provides an up to 8-input OR algorithm, meaning that it performs the inclusive OR Boolean function. Each input (IN [1],
IN [2], ..., IN [8]) has the capability of being optionally inverted, if required.
Function
Turns the digital output (OUT) ON if any one input (IN [1], IN [2], ..., IN [8]) is ON; therefore:
If all inputs are OFF, then: OUT = OFF.
If any one input is ON, then: OUT = ON.
Truth Table
IN [1]
OFF
ON
OFF
ON
IN [2]
OFF
OFF
ON
ON
Inputs
IN [1..8] = Boolean value
Outputs
OUT = Boolean value controlled by the status of input signals.
Parameters
IN [1..8]
INPTINVSTS [1..8]
Description
Provides a fixed pulse output (OUT) each time the input (IN) transitions from OFF to ON. You specify the fixed output
pulse width (PULSEWIDTH) in seconds through configuration.
Function
Used to define the fixed output (OUT) pulse width.
•
If the input (IN) pulse time is less than or equal to the fixed PULSEWIDTH time, output (OUT) pulse width equals
the fixed PULSEWIDTH time.
•
If the IN pulse time is greater than the fixed PULSEWIDTH time, OUT pulse width is restricted to the fixed
PULSEWIDTH time. Another output pulse cannot be generated until the preceding pulse has completed.
Inputs
IN = Boolean value
Outputs
OUT = Boolean value
Parameters
IN
ORDERINCM
OUT
PULSEWIDTH
Summary of Contents for ProcessLogix 1756-IA16
Page 1: ...ProcessLogix Function Blocks 1757 Series Reference Manual Spare Allen Bradley Parts...
Page 2: ......
Page 40: ...Publication 1757 RM810A EN P May 2002 2 20 Physical Equipment Blocks...
Page 116: ...Publication 1757 RM810A EN P May 2002 3 76 Functional Blocks...
Page 119: ...Spare Allen Bradley Parts...