Programming and Parameters
3-21
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22B-UM001I-EN-E
Advanced Program Group
(continued)
A066 [Analog Out High]
Related Parameter(s):
Scales the Maximum Output Value for the
[Analog Out Sel] source setting.
Examples:
Values
Default:
100%
Min/Max:
0/800%
Display:
1%
A066 Setting
A065 Setting
A065 Max. Output Value
50%
1 “OutCurr 0-10”
5V for 200% Drive Rated Output Current
90%
8 “OutPowr 0-20”
18mA for 200% Drive Rated Power
A067 [Accel Time 2]
Related Parameter(s):
,
,
-
When active, sets the rate of acceleration for all speed increases except jog. Refer to the flowchart on
page
for details.
Values
Default:
20.0 Secs
Min/Max:
0.0/600.0 Secs
Display:
0.1 Secs
Maximum Freq
Accel Time
Accel Rate
=
Speed
0
Time
P035 [Maximum Freq]
P039 or A067
[Accel Time x]
P040 or A068
[Decel Time x]
0
Acceler
ation
Deceler
ation
22B-UM001.book Page 21 Tuesday, May 30, 2017 5:22 PM
Aotewell Ltd
www.aotewell.com Industry Automation
HongKong|UK|China [email protected]