Overview
P-5
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Catalog Number Explanation
a
Drive
Code
Type
20L
PowerFlex 700L
b
Voltage Rating
Code
Voltage
Ph.
C
400V AC
3
D
480V AC
3
E
600V AC
3
F
690V AC
3
c1
ND Rating
400V, 60 Hz Input
Code
Amps
Hp (KW)
Frame
360
360
268 (200)
2
650
650
500 (370)
3A
1K2
1250
960 (715)
3B
c2
ND Rating
480V, 60 Hz Input
Code
Amps
Hp (KW)
Frame
360
360
300 (224)
2
650
650
600 (445)
3A
1K2
1250
1150 (860)
3B
c3
ND Rating
600V, 60 Hz Input
Code
Amps
Hp (KW)
Frame
425
425
465 (345)
3A
800
800
870 (650)
3B
1K1
1175
1275 (950)
3B
♣
♣
Must operate at 2 kHZ PWM only, and only as a
stand-alone inverter module (“K” in position 13).
c4
ND Rating
690V, 60 Hz Input
Code
Amps
Hp (KW)
Frame
380
380
475 (355)
3A
705
705
881 (657)
3B
1K0
1050
1310 (980)
3B
♣
♣
Must operate at 2 kHZ PWM only, and only as a
stand-alone inverter module (“K” in position 13).
Position
1-3
4
5-7
8
9
10
11
12
13
14
15
16
17
18
20L
E
800
A
0
E
N
N
A
N
1
0
W
A
a
b
c
d
e
f
g
h
i
j
k
l
m
n
d
Enclosure
Code
Type
Conformal
Coating
A
NEMA/UL Type 1, IP20
✝
No
N
Open-Chassis Style/IP00
❖
No
✝
Frame 3 complete drive.
❖
Frame 2 drive and Frame 3 input filter and power
modules.
e
HIM
Code
Operator Interface
0
No HIM/Blank Cover
3
Full Numeric LCD
♠
C
Door-Mounted Full Numeric LCD
✝
♠
Frame 2 and Frame 3 power modules.
✝
Frame 3 complete drive only.
f
Documentation
Code
Documents
Ship Carton
E
English Doc Set
Yes
N
No Documentation
Yes
Q
No Documentation
No
g
Brake
Code
w/Brake IGBT
N
No
h
Brake Resistor
Code
w/Resistor
N
No
i
Equipment Type
Code
Description
Frame
A
Complete Regenerative
Drive - Std. Interrupt Rating
2, 3A, and 3B
C
Input Filter
3A and 3B
E
Combined Active Converter/
Inverter Power Module
3A only
G
Active Converter
Power Module
3B only
J
Inverter Power Module -
Coupled Version
3B only
K
Inverter Power Module -
Common DC Bus Version
3B only
L
Dual Inverter Power Module
3A only
P
Active Converter Power
Module - Stand Alone Version
3B only
X
Spare Power Module
◆
3A and 3B
◆
No control cassettes.
j
Comm Slot
Code
Communication Option
DPI
User-Installed
Kit Cat. No.
✧
N
None
N
C
ControlNet (Coax) - DPI
‡
20-COMM-C
D
DeviceNet - DPI
‡
20-COMM-D
E
EtherNet/IP - DPI
‡
20-COMM-E
1
DriveLogix Comm Option,
ControlNet (Coax)
✽
—
2
DriveLogix Comm Option,
ControlNet Redundant (Coax)
✽
—
3
DriveLogix Comm Option,
ControlNet (Fiber)
✽
—
4
DriveLogix Comm Option,
ControlNet Redundant (Fiber)
✽
—
5
DriveLogix Comm Option,
DeviceNet (Open
Connection)
✽
—
6
DriveLogix Comm Option,
DeviceNet (Twisted Pair)
✽
—
✧
For 700S Phase II Control with DriveLogix5730,
comm. slot option selections are mutually
exclusive. For two communication adapters, (DPI
and DriveLogix), select the DriveLogix comm.
slot option and order the DPI user installed kit
catalog number separately.
‡
700 Vector Control uses DPI comm. slot options
only.
✽
DriveLogix comm. slot options require 700S
Phase II Control with DriveLogix5730.
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
+86-755-8660-6182