Troubleshooting
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Manually Clearing Faults
To manually clear faults, follow these steps.
1.
Press the
(Escape) key to acknowledge the fault.
The fault information is removed so that you can use the HIM.
2.
Address the condition that caused the fault.
The cause must be corrected before the fault can be cleared.
3.
After corrective action has been taken, clear the fault by using
one
of
these methods:
•
Press the
(
Stop) key.
•
Cycle drive power.
•
Set parameter 239 - [Fault Clear] to “1” (Clear Faults).
•
“Clear Faults” on the HIM Diagnostic menu.
Converter Faults
When a fault is generated in the Converter, that fault is passed to the Inverter
so all the faults are recorded in the Inverter fault queue. Faults in the
converter are numbered 1 to 99.
When using PowerFlex 700 Vector Control, the fault from the Converter is
added to a base number of 300, so all the Converter faults are numbered 301
to 399. The pop-up window on the HIM alerts the user to look at the fault
log in the PF700AC to get the specific fault text.
When using PowerFlex 700S Phase II Control, the faults from the Converter
are all combined into one fault code (F110) in the Inverter. The pop-up
window on the HIM alerts the user to look at the fault log in the PF700AC
to get the specific fault text.
For a complete listing of Converter faults, descriptions, and actions, see the
PowerFlex 700L Active Converter User Manual, publication
PFLEX-UM002.
Esc
- Fault - F
3
40
F
3
40
S
ee PF700AC
Time
S
ince Fault
00000:00:01
- Fault - F 110
700L Cnv Faulted
Time
S
ince Fault
00000:00:01