22
Rockwell Automation Publication 7000-UM203C-EN-P - September 2018
Chapter 3
Operation, Installation, and Wiring
Figure 7 - Functional Safety Mode
SPS Jumper Settings
See
Figure 12
for SPS jumper location on the OIBBS.
1. Ensure the SPS jumper on the rectifier OIBBS is installed if the drive is
installed with an SPS rectifier.
2. Ensure the SPS jumper on the inverter OIBBS is not installed.
Commissioning
Follow the commissioning procedure in the user manual pertaining to the drive
frame size (see
Additional Resources on page 6
).
Table 5 - Parameter Settings
Group
Parameter Name
Status
Drive Hardware Group
Number of Devices (P145/P146)
Number of installed OIB2s
Rectifier Type (P153)
6 PWM
Bypass Contactor (Hardware Options 1 – P141)
Unchecked
Redundant Devices (Hardware Options 1 – P141)
Unchecked
SPS Drive (Hardware Options 2– P274)
Must match SPS jumper on
rectifier OIBBS
Parallel Drive Group
Drives in System (P745)
Set to 1
Powerup Config (P717)
Single
Feature Select Group
Synchronous Transfer (Special Features – P99)
Unchecked
IMPORTANT
When using the System Test mode with the STO option and an SPS rectifier,
follow input device interlock requirements.
Summary of Contents for PowerFlex 7000 Series