Component Test Procedures
Chapter 2
Visual Component Inspection
Visually inspect the circuit boards and power components before energizing
the drive for any of the component test procedures.
1. Read the General Safety Precautions on page
2. Remove power from the drive (see page
3. Remove the protective covers from the drive (see page
4. Check components for burn marks, breakage, or foil delamination on all
circuit boards.
Replace any of these components without further testing if they show evidence
of burn marks, breakage, or foil delamination.
Troubleshoot a Control
Power Supply Failure
If a drive Power Failure fault (F3) has occurred and the drive is inoperable by
using the HIM or other means of control, a control power failure can have
occurred. Compete these steps to determine where the control power failure
has occurred.
1. Read the General Safety Precautions on page
2. Remove the protective covers from the drive (see page
3. If installed, remove the resolver feedback option module (see page