Rockwell Automation Publication 20P-TG001C-EN-P - February 2018
63
Part Replacement Procedures
Chapter 3
8. Record all switch and jumper settings on the control board. See the
PowerFlex DC Digital Drive User Manual, publication
for more information.
Jumper/
Switch
Function
Setting
S4
Configures the input voltage of the DC analog tachometer.
S9
Configures the input signal of analog input 1 (terminals 1 and 2):
Note: The same input signal type must be programmed in Par 71 [Anlg In1 Config].
S10
Configures the input signal of analog input 2 (terminal 3 and 4):
Note: The same input signal type must be programmed in Par 76 [Anlg In2 Config].
S11
Configures the input signal of analog input 3 (terminals 5 and 6):
Note: The same input signal type must be programmed in Par 81 [Anlg In3 Config].
S14
Field current resistors setting.
In addition, the value that is selected with switch S14 must be entered in Par 374
[Rated Field Curr] in the control software when the drive is commissioned.
S14-1 =
S14-2 =
S14-3 =
S14-4 =
S14-5 =
S14-6 =
S15
Configuration of the control circuit board to the appropriate drive size. This value is
set to the appropriate size at the factory.
S15-1 =
S15-2 =
S15-3 =
S15-4 =
S15-5 =
S15-6 =
S15-7 =
S15-8 =
S20
Monitoring of the Z channel of the digital encoder on connector XE2:
Off Position
Z-channel monitored
On Position
Z-channel not monitored
S21
Encoder power supply voltage and input adaptation selection:
Note: When control power is supplied to the drive, the appropriate LED lights to
indicate the selection of the switch.
ENC_5
+5V encoder (+2.5…5.4V input range)
ENC_12
+12…15 V encoder (+5.4V…15.2V input range)