Rockwell Automation Publication 1734-IN043B-EN-E - January 2019
21
POINT I/O 4 Channel IO-Link Master Module
Dimensions, approx., HxWxD
56 x 12 x 75.5 mm
(2.21 x 0.47 x 2.97 in.)
Weight, approx.
36 g (1.27 oz)
Enclosure type rating
None (open-style)
Keyswitch position
2
(1)
Use this Conductor Category information for planning conductor routing as described in the appropriate System Level
Installation Manual. Also refer to Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1
, for
more information.
POINT I/O 4 Channel IO-Link Master Module 1734-4IOL – Standard Digital Input
Attribute
Value
Backplane power
5V DC, 100 mA
Input ratings
24V DC, 12 mA
On-state voltage, min
11V DC
On-state current, min
2.0 mA
On-state current, max
7.0 mA
Off-state voltage, max
5V DC
Off-state current, min
1.5 mA
Input filter
ON to OFF
OFF to ON
Each input independently settable in 1 ms intervals.
Default value is 1 ms.
0...65 ms
0...65 ms
POINT I/O 4 Channel IO-Link Master Module 1734-4IOL – Standard Digital Output
Attribute
Value
Backplane power
5V DC, 100 mA
Output ratings, per channel
24V DC, 0.15 A
Output ratings, per module, max
24V DC, 0.6 A
On-state voltage, min
19.2V DC
On-state voltage, max
28.8V DC
General Specifications
Attribute