Rockwell Automation Publication 1734-IN043B-EN-E - January 2019
POINT I/O 4 Channel IO-Link Master Module
Interpret Status Indicators
See the following diagram and table for information on how to interpret the
status indicators.
POINT I/O 4 Channel IO-Link Master Module – 1734-4IOL
b+1...c
Input data from Channel 2
(2)
c+1...d
Input data from Channel 3
(2)
(1) Channel status:
Bit 0: 0 = Roll-up status, an OR of bits 1...7
Bit 1: 0 = Connection to device, 1 = No connection to device
Bit 2: 1 = Configuration to device in progress
Bit 3: 1 = Device configuration failed
Bit 4: 1 = IO-Link key failure
Bit 5: 1 = DO short circuit
Bit 6: 1 = Process data invalid
Bit 7: 1 = Low-power fault
Bit 8: 1 = IO-Link output value is forced to limit
Bit 9...15: Reserved
(2) Produced sizes can be in the range of 0...32. Input data for each channel always begin on a 32-bit
boundary, and is enforced by software using the data description for the channel.
Default Data Map for 1734-4IOL – Produced Assembly Instance 102
Message Size: 0...132 Bytes
Consumed Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
7
1
3
0
2
Module
Status
Network
Status
24V DC
SIO
IO
LINK
1734-4IOL
1
3
0
2
1
3
0
2
NODE:
NODE:
Module status
Network status
Status of standard digital I/O 0
Status of standard digital I/O 1
Status of standard digital I/O 2
Status of standard digital I/O 3
Status of IO-Link 0
Status of IO-Link 1
Status of IO-Link 2
Status of IO-Link 3