Rockwell Automation Publication 1734-IN043B-EN-E - January 2019
17
POINT I/O 4 Channel IO-Link Master Module
50
Channel 3 input off to on time delay
(2)
51
Channel 3 input on to off time delay
(2)
(1) Fault and idle conditions are only valid when the channel is configured for IO-Link or DO. Mode and Value
behavior is defined in the IO-Link Channel object specification.
(2) Time delays are specified in 1 ms increments, valid range is 0...65 (a value of zero disables the
input filter).
Default Data Map for 1734-4IOL – Consumed Assembly Instance 101
Message Size: 0...128 Bytes
Consumed Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0...a
Output data for Channel 0
(1)
a+1...b
Output data for Channel 1
(1)
b+1...c
Output data for Channel 2
(1)
c+1...d
Output data for Channel 3
(1)
(1) Consumed sizes can be in the range of 0...32. Output data for each channel always begin on a 32-bit
boundary, and is enforced by software using the data description for the channel.
Default Data Map for 1734-4IOL – Produced Assembly Instance 102
Message Size: 0...132 Bytes
Consumed Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Channel 0 status
(1)
2
Channel 1 status
(1)
4
Channel 2 status
(1)
6
Channel 3 status
(1)
8
Channel 0 most recent event
12
Channel 1 most recent event
16
Channel 2 most recent event
20
Channel 3 most recent event
24...a
Input data from Channel 0
(2)
a+1...b
Input data from Channel 1
(2)
Default Data Map for 1734-4IOL – Configuration Assembly Instance 100
Message Size: 46 Bytes
Consumed Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0