Allen-Bradley POINT I/O 1734-4IOL Installation Instructions Manual Download Page 1

Installation Instructions

Original Instructions

POINT I/O 4 Channel IO-Link Master Module

Catalog Number 1734-4IOL

Topic Page

Important User Information

2

Environment and Enclosure

3

Prevent Electrostatic Discharge

4

Special Conditions for Safe Use

5

About the Module

6

Install the Mounting Base

9

Install the Module

9

Install the Removable Terminal Block

11

Remove a Mounting Base

13

Wire the Module

14

Communicate with the Module

16

Interpret Status Indicators

18

Specifications

20

Summary of Contents for POINT I/O 1734-4IOL

Page 1: ...nformation 2 Environment and Enclosure 3 Prevent Electrostatic Discharge 4 Special Conditions for Safe Use 5 About the Module 6 Install the Mounting Base 9 Install the Module 9 Install the RemovableTe...

Page 2: ...with any particular installation Rockwell Automation Inc cannot assume responsibility orliability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automatio...

Page 3: ...by the use of a tool Subsequent sections of this publication may contain more information regardingspecific enclosure type ratings that are required to comply with certain product safety certification...

Page 4: ...an approved grounding wriststrap Do not touch connectors or pins on component boards Do not touch circuit components inside the equipment Use a static safe workstation if available Store the equipment...

Page 5: ...nd anchors appropriately Be sure to ground the DIN rail properly Refer to Industrial AutomationWiring and Grounding Guidelines publication1770 4 1 for more information Do not remove or replace an Adap...

Page 6: ...pplication In IO Link mode the module supports four channels for IO Link master communication with IO Link compatible devices In standard digital I O mode the module supports four channels of digital...

Page 7: ...s 3 Insertable I O module 8 Mechanical keying orange 4 Removable terminal block RTB handle 9 DIN rail locking screw orange 5 Removable terminal block 10 Module wiring diagram Analog Voltage Output Mod...

Page 8: ...inal Base Description Description 1 Module locking mechanism 6 Interlocking side pieces 2 Slide in writable label 7 Mechanical keying orange 3 Insertable I O module 8 DIN rail locking screw orange 4 T...

Page 9: ...locking side pieces to engage the adjacent module or adapter 3 Press firmly to seat the mounting base on the DIN rail The mounting base snaps into place Be sure that the orange DIN rail locking screw...

Page 10: ...nstalled aligns with the notch in the base 2 Make certain the DIN rail locking screw is in the horizontal position You cannot insert the module if the locking mechanism is unlocked 3 Insert the module...

Page 11: ...opposite the handle into the base unit This end has a curved section that engages with the wiring base 2 Rotate the terminal block into the wiring base until it locks itself in place WARNING Whenyouco...

Page 12: ...to place on the module WARNING For 1734 RTBS and 1734 RTB3S to latch and unlatch the wire insert a bladed screwdriver catalog number 1492 N90 3 mm diameter blade into theopeningatapproximately73 blade...

Page 13: ...nal block 3 Press the module lock on the top of the module 4 Pull on the I O module to remove from the base 5 Repeat steps 1 2 3 and 4 for the module to the right 6 Use a small bladed screwdriver to r...

Page 14: ...Link Master Module 1734 4IOL POINT I O 4 Channel IO Link Master ModuleWiring IO Link Mode Channel Common Voltage 0 4 6 1 5 7 2 4 6 3 5 7 Power is supplied through the internal power bus 1734 4IOL Cha...

Page 15: ...Channel Input Common Voltage Channel 0 0 4 6 Channel 1 1 5 7 Channel 2 2 4 6 Channel 3 3 5 7 Connect common on 3 wire inputs Power is supplied through the internal power bus Channel Output Common Vol...

Page 16: ...Default Data Map for 1734 4IOL Configuration Assembly Instance 100 Message Size 46 Bytes Consumed Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 36 Channel 0 fault mode 1 37 Channel 0 idle mode...

Page 17: ...b Output data for Channel 1 1 b 1 c Output data for Channel 2 1 c 1 d Output data for Channel 3 1 1 Consumed sizes can be in the range of 0 32 Output data for each channel always begin on a 32 bit bou...

Page 18: ...rcuit Bit 6 1 Process data invalid Bit 7 1 Low power fault Bit 8 1 IO Link output value is forced to limit Bit 9 15 Reserved 2 Produced sizes can be in the range of 0 32 Input data for each channel al...

Page 19: ...line and has connections in the established state Flashing red One or more I O connections are in timed out state Red Critical link failure failed communication device Device detected error that preve...

Page 20: ...C Thermal dissipation max 5 12 BTU hr 28 8V DC Isolation voltage 50V continuous basic insulation type Tested at 2121V DC for 60 s field side to system No isolation between individual channels Field po...

Page 21: ...I O 4 Channel IO Link Master Module 1734 4IOL Standard Digital Input Attribute Value Backplane power 5V DC 100 mA Input ratings 24V DC 12 mA On state voltage min 11V DC On state current min 2 0 mA On...

Page 22: ...20 55 C 4 131 F Temperature nonoperating IEC 60068 2 1 Test Ab unpackaged nonoperating cold IEC 60068 2 2 Test Bb unpackaged nonoperating dry heat IEC 60068 2 14 Test Na unpackaged nonoperating therm...

Page 23: ...Control Equipment certified for US and Canada See UL File E322657 CE European Union 2014 30 EU EMC Directive compliant with EN 61326 1 Measurement Control Laboratory use Industrial requirements EN 61...

Page 24: ...24 Rockwell Automation Publication 1734 IN043B EN E January 2019 POINT I O 4 Channel IO Link Master Module Notes...

Page 25: ...Rockwell Automation Publication 1734 IN043B EN E January 2019 25 POINT I O 4 Channel IO Link Master Module Notes...

Page 26: ...26 Rockwell Automation Publication 1734 IN043B EN E January 2019 POINT I O 4 Channel IO Link Master Module Notes...

Page 27: ...t User Forums and Product Notification Updates www rockwellautomation com knowledgebase LocalTechnical Support Phone Numbers Locate the phone number for your country www rockwellautomation com global...

Page 28: ...Otomasyon Ticaret A Kar Plaza Merkezi E Blok Kat 6 34752 erenk y stanbul Tel 90 216 5698400 Rockwell Automation maintains current product environmental information on its website at http www rockwella...

Reviews: