Chapter 3
MMS and Your Coprocessor
3-11
Output Image (O) Mappings
The table that follows provides sample mappings of output image data
types, where:
O:000/x,n is a bit–string of length n starting at bit x (octal) of the specified
word.
Important: Note that addressing in the Output Image Mapping is in octal.
This does not pertain to the ‘‘size” information. For example,
‘‘O:003/5,10” specifies a bit string of length 10 (vs. length 8).
Address:
MMS Data Type:
O:000
BIT STRING (16 bits)
O:001,25
BIT STRING (25 bits)
O:000/10
BOOLEAN
O:001/3,5
BIT STRING (5 bits)
See the section titled Additional Information on Using Data Types, later in
this chapter, and Appendix A of this manual for more information on
mapping MMS data types onto PLC–5 data files.
Block Transfer (BT) Mappings
The following is the format of a block transfer control structure as viewed
by MMS:
BOOLEAN
RW
BOOLEAN
TO
BOOLEAN
NR
BOOLEAN
EW
BOOLEAN
CO
BOOLEAN
ER
BOOLEAN
DN
BOOLEAN
ST
BOOLEAN
EN
INTEGER
RLEN (16 bits)
INTEGER
DLEN (16 bits)
INTEGER
FILE (16 bits)
INTEGER
ELEM(16 bits)
INTEGER
RGS (16 bits)
Important: Refer to your PLC–5 Programming Reference Manual for
descriptions of the individual fields in data type structures.
Summary of Contents for PLC-5 MAP/OSI
Page 1: ...PLC 5 MAP OSI Software User Manual Cat No 1785 OSI AB Parts...
Page 4: ...Table of Contents iii OSI Layer Management E 1...
Page 57: ...Chapter 4 Basic Programming Techniques 4 7 For example B7 6 10 AB Parts...
Page 91: ...Mapping MMS Data Types onto PLC 5 40 5 60 File Types Appendix A A 2 T ACC D 16 AB Parts...