Appendix B
RSLogix 5000® Sample Code
2. Add an MSG function block to the program, browse to the
Run_Time_Message
data type created in step 1. To configure the
message instruction, double-click the gray box.
Figure 22
3. In the
Configuration
tab select:
Message type - CIP Generic
Service Type - Get Attribute Single
Service Code - (Automatically populated)
Destination Element - Run_Time_Seconds (browse to this tag)
Instance - 1
Class - 23*
Attribute 32*
* hexadecimal values