Chapter
5
Produce and Consume Tags
(interlock controllers)
This chapter explains how to interlock (produce and consume tags) controllers
via a ControlNet network.
Topic
Page
Determine Connections for Produced and Consumed Tags
Organize Tags for Produced or Consumed Data
Adjust for Bandwidth Limitations
Interlocking controllers is the preferred method of sharing scheduled data
between controllers when data needs to be delivered regularly, quickly and at a set
interval.
Terminology
A Logix5000 controller lets you produce (broadcast) and consume (receive)
system-shared tags.
Term
Definition
Produced tag
A tag that a controller makes available for use by other controllers. Multiple
controllers can simultaneously consume (receive) the data. A produced tag
sends its data to one or more consumed tags (consumers) without using logic.
The produced tag sends its data at the RPI of the fastest consuming tag.
Consumed tag
A tag that receives a produced tag’s data. The data type of the consumed tag
must match the data type, including any array dimensions, of the produced
tag. The RPI of the fastest consumed tag determines the rate at which the
produced tag is produced.
For two controllers to share produced or consumed tags, they must reside on the
same ControlNet network.
Rockwell Automation Publication CNET-
UM001E-EN-P - June 2016
71
Summary of Contents for ControlNet Compact GuardLogix 1769
Page 4: ...SummaryofChanges Notes 4 Rockwell Automation Publication CNET UM001E EN P June 2016...
Page 8: ...Preface Notes 8 Rockwell Automation Publication CNET UM001E EN P June 2016...
Page 70: ...Chapter 4 ControlI O Notes 70 Rockwell Automation Publication CNET UM001E EN P June 2016...
Page 99: ......