Configure a ControlNet Module
Chapter 3
9.
To change the network properties from default settings to those that best
fit your network, from the Network menu, choose Properties.
10.
On the Network Parameters tab, configure the network parameters, as
described in the table below, and click OK.
Parameter
Description
Network Update Time (ms)
The smallest user-configurable repetitive time cycle at which data can
be sent on a ControlNet network.
Max Scheduled Address
This is the node with the highest network address that can use
scheduled time on a ControlNet link. I/O data is transferred during
scheduled time. RSNetWorx for ControlNet software sets this value.
We recommend that you not change it.
Max Unscheduled Address
Node with the highest network address that can use unscheduled
time on a ControlNet link. Messaging data is transferred during
unscheduled time.
Nodes set at addresses higher than the maximum unscheduled node
do not communicate on the network. For example, they will not
display in RSLinx software.
Media Redundancy
Designates if the network uses media redundancy.
Network Name
User-defined name of the network.
Rockwell Automation Publication CNET-
UM001E-EN-P - June 2016
47