Publication 1756-UM001E-EN-P - August 2002
Communicate with Another Controller over an EtherNet/IP Network
5-23
Access ControlLogix Data
Complete this task for any message that a PLC-5 or SLC 5/05 controller
sends to a ControlLogix controller over an EtherNet/IP network.
A.
Using either RSLogix 5 or RSLogix 500 software, as required,
open the project for the PLC-5 or SLC 5/05 controller.
B.
If the message is from a SLC 5/05 controller, in the MSG
instruction, select
PLC5
.
C.
Display the set-up screen for the message.
D.
Specify the following parameters:
IMPORTANT
This procedure uses RSLogix 5
™
or RSLogix 500
™
software, revision 3.x.
MSG
Read/Write Message
Type
Peer-To-Peer
Read/Write
Read
Target Device
PLC5
Local/Remote
Local
Control Block
N7:0
Control Block Length
93
Setup Screen
MSG
42474
If the controller
is a:
For this section:
And this item:
Specify:
PLC-5
This PLC-5
Communication Command
PLC-5 Typed Read
or
PLC-5 Typed Write
Data Table Address
starting address of the data in the PLC-5 controller
Size in Elements
number of elements to read or write
Port Number
2
Target Device
Data Table Address
Type, in quotation marks [“ “], the name of the tag in the
ControlLogix controller (e.g., “count”).
MultiHop
Select
Yes
.
SLC 500
This Controller
Communication Command
PLC5 Read
or
PLC5 Write
Data Table Address
starting address of the data in the SLC 500 controller
Size in Elements
number of elements to read or write
Channel
1
Target Device
Data Table Address
Type, in quotation marks [“ “], the name of the tag in the
ControlLogix controller (e.g., “count”).
MultiHop
Select
Yes
.
Summary of Contents for controllogix 1756-L63
Page 1: ...ControlLogix System 1756 L1 L1Mx L55Mxx L63 User Manual Allen Bradley HMIs...
Page 4: ...Publication 1756 UM001E EN P August 2002 Summary of Changes 2 Notes...
Page 16: ...Publication 1756 UM001E EN P August 2002 Table of Contents x...
Page 268: ...Publication 1756 UM001E EN P August 2002 15 4 Monitor Connections Notes...
Page 276: ...Publication 1756 UM001E EN P August 2002 16 8 Communicate with a DeviceNet Device Notes...
Page 402: ...Publication 1756 UM001E EN P August 2002 24 22 Program Motion Control Notes...
Page 408: ...Publication 1756 UM001E EN P August 2002 25 6 Maintain the 1756 BA1 Battery Notes...
Page 418: ...Publication 1756 UM001E EN P August 2002 B 2 Estimate Execution Time...
Page 420: ...Publication 1756 UM001E EN P August 2002 C 2 Estimate Memory Use...
Page 422: ...Publication 1756 UM001E EN P August 2002 D 2 Determine When Data Is Updated Notes...
Page 424: ...Publication 1756 UM001E EN P August 2002 E 2 Reconfigure an I O module Notes...
Page 428: ...Publication 1756 UM001E EN P August 2002 4 Index...
Page 429: ...Publication 1756 UM001E EN P August 2002 Index 5 Allen Bradley HMIs...
Page 430: ...Publication 1756 UM001E EN P August 2002 6 Index...
Page 435: ...ControlLogix System User Manual Allen Bradley HMIs...