Publication 1756-UM001E-EN-P - August 2002
Communicate with 1756 I/O over a ControlNet™ Network
8-7
F.
Select a
Comm Format
:
IMPORTANT
If the module is also in the I/O configuration of
another controller, then select the
Listen Only
version
of the Comm Format (e.g.,
Listen Only - Input Data
).
If this module is a:
And:
And you want to:
Then select:
diagnostic digital input
Full Diagnostics - Input Data
non-diagnostic digital input
local chassis
time stamp a change in data
CST Timestamped Input Data
omit time stamps
Input Data
remote chassis
Rack Optimization
diagnostic digital output
schedule when to apply outputs
Full Diagnostics - Scheduled
Output Data
not schedule when to apply
outputs
Full Diagnostics - Output Data
fused digital output
schedule when to apply outputs
CST Timestamped Fuse Data -
Scheduled Output Data
not schedule when to apply
outputs
CST Timestamped Fuse Data -
Output Data
non-diagnostic and non-fused
digital output
local chassis
schedule when to apply outputs
Scheduled Output Data
not schedule when to apply
outputs
Output Data
remote chassis
Rack Optimization
non-isolated analog input
floating point mode provides
sufficient sample time
time stamp when the data is
sampled
CST Timestamped Float Data -
wiring_mode
omit the time stamp
Float Data -
wiring_mode
floating point mode
does not
provide sufficient sample time
time stamp when the data is
sampled
CST Timestamped Integer Data -
wiring_mode
omit the time stamp
Integer Data -
wiring_mode
isolated or temperature
measuring analog input
25 ms sample time or greater is
sufficient
time stamp when the data is
sampled
CST Timestamped Float Data
omit the time stamp
Float Data
sample time must be less than
25 ms
time stamp when the data is
sampled
CST Timestamped Integer Data
omit the time stamp
Integer Data
analog output
associated inputs are REALs
time stamp the data echo
CST Timestamped Float Data
omit the time stamp
Float Data
associated inputs are INTs
time stamp the data echo
CST Timestamped Integer Data
omit the time stamp
Integer Data
Summary of Contents for controllogix 1756-L63
Page 1: ...ControlLogix System 1756 L1 L1Mx L55Mxx L63 User Manual Allen Bradley HMIs...
Page 4: ...Publication 1756 UM001E EN P August 2002 Summary of Changes 2 Notes...
Page 16: ...Publication 1756 UM001E EN P August 2002 Table of Contents x...
Page 268: ...Publication 1756 UM001E EN P August 2002 15 4 Monitor Connections Notes...
Page 276: ...Publication 1756 UM001E EN P August 2002 16 8 Communicate with a DeviceNet Device Notes...
Page 402: ...Publication 1756 UM001E EN P August 2002 24 22 Program Motion Control Notes...
Page 408: ...Publication 1756 UM001E EN P August 2002 25 6 Maintain the 1756 BA1 Battery Notes...
Page 418: ...Publication 1756 UM001E EN P August 2002 B 2 Estimate Execution Time...
Page 420: ...Publication 1756 UM001E EN P August 2002 C 2 Estimate Memory Use...
Page 422: ...Publication 1756 UM001E EN P August 2002 D 2 Determine When Data Is Updated Notes...
Page 424: ...Publication 1756 UM001E EN P August 2002 E 2 Reconfigure an I O module Notes...
Page 428: ...Publication 1756 UM001E EN P August 2002 4 Index...
Page 429: ...Publication 1756 UM001E EN P August 2002 Index 5 Allen Bradley HMIs...
Page 430: ...Publication 1756 UM001E EN P August 2002 6 Index...
Page 435: ...ControlLogix System User Manual Allen Bradley HMIs...