1
Publication 1756-UM001E-EN-P - August 2002
Chapter
5
Communicate with Another Controller over an
EtherNet/IP Network
When to Use This
Procedure
Use this procedure to transfer data from one controller to another
controller over an EtherNet/IP network:
•
ControlLogix controller to another ControlLogix controller
•
ControlLogix controller to a PLC-5E
®
or SLC 5/05
™
controller
•
PLC-5E or SLC 5/05 controller to a ControlLogix controller
Before You Begin
Before you use this procedure, do the following:
1.
To produce and consume tags over an EtherNet/IP network, you
must use 1756-ENBx or -ENET/B modules. If you have a
1756-ENET/A module, determine if you can update the module:
2.
Configure the ENB or ENET modules. Refer to "Configure an
EtherNet/IP Module" on page 1-1.
switch
SLC 5/05 Controller
42607
ControlLogix Controller
ControlLogix Controller
PLC-5E Controller
For this 1756-ENET/A revision:
Then:
1.18 or later (latch of the RJ--45
connector points to the left)
Update the firmware of module to
revision 2.6 or later.
earlier than 1.18 (latch of the RJ--45
connector points to the right)
Contact your Rockwell Automation
representative or local distributor.
Summary of Contents for controllogix 1756-L63
Page 1: ...ControlLogix System 1756 L1 L1Mx L55Mxx L63 User Manual Allen Bradley HMIs...
Page 4: ...Publication 1756 UM001E EN P August 2002 Summary of Changes 2 Notes...
Page 16: ...Publication 1756 UM001E EN P August 2002 Table of Contents x...
Page 268: ...Publication 1756 UM001E EN P August 2002 15 4 Monitor Connections Notes...
Page 276: ...Publication 1756 UM001E EN P August 2002 16 8 Communicate with a DeviceNet Device Notes...
Page 402: ...Publication 1756 UM001E EN P August 2002 24 22 Program Motion Control Notes...
Page 408: ...Publication 1756 UM001E EN P August 2002 25 6 Maintain the 1756 BA1 Battery Notes...
Page 418: ...Publication 1756 UM001E EN P August 2002 B 2 Estimate Execution Time...
Page 420: ...Publication 1756 UM001E EN P August 2002 C 2 Estimate Memory Use...
Page 422: ...Publication 1756 UM001E EN P August 2002 D 2 Determine When Data Is Updated Notes...
Page 424: ...Publication 1756 UM001E EN P August 2002 E 2 Reconfigure an I O module Notes...
Page 428: ...Publication 1756 UM001E EN P August 2002 4 Index...
Page 429: ...Publication 1756 UM001E EN P August 2002 Index 5 Allen Bradley HMIs...
Page 430: ...Publication 1756 UM001E EN P August 2002 6 Index...
Page 435: ...ControlLogix System User Manual Allen Bradley HMIs...