Publication 1756-UM001E-EN-P - August 2002
3-12
Communicate with 1756 I/O over an EtherNet/IP Network
Create Aliases
In this task, you convert tags in your programs to aliases for I/O
points or channels (devices). As an alias for an I/O point or channel,
each tag:
•
provides a descriptive name for the device that is wired to the
point or channel
•
represents the value of the point or channel. When one changes,
the other reflects the change.
A.
From the
Logic
menu, select
Edit Tags
.
EXAMPLE
Create aliases
The following logic was initially programmed using descriptive tag names, such as
start
and
motor
. Later, the tags were converted to aliases for the corresponding I/O devices.
start
is an alias for the push button that is wired to point 1 of the
module that is in slot 2 of the local chassis. When the push button
is on,
start
is on.
motor
is an alias for the starter contactor that is wired to point 0 of
the module that is in slot 0 of a remote chassis (named conveyor).
When
motor
turns on, the starter contactor turns on.
motor
<conveyor:0:O.Data.0>
motor
<conveyor:0:O.Data.0>
start
<Local:2:I.Data.1>
stop
<Local:2:I.Data.0>
42435
B.
C.
42421
Summary of Contents for controllogix 1756-L63
Page 1: ...ControlLogix System 1756 L1 L1Mx L55Mxx L63 User Manual Allen Bradley HMIs...
Page 4: ...Publication 1756 UM001E EN P August 2002 Summary of Changes 2 Notes...
Page 16: ...Publication 1756 UM001E EN P August 2002 Table of Contents x...
Page 268: ...Publication 1756 UM001E EN P August 2002 15 4 Monitor Connections Notes...
Page 276: ...Publication 1756 UM001E EN P August 2002 16 8 Communicate with a DeviceNet Device Notes...
Page 402: ...Publication 1756 UM001E EN P August 2002 24 22 Program Motion Control Notes...
Page 408: ...Publication 1756 UM001E EN P August 2002 25 6 Maintain the 1756 BA1 Battery Notes...
Page 418: ...Publication 1756 UM001E EN P August 2002 B 2 Estimate Execution Time...
Page 420: ...Publication 1756 UM001E EN P August 2002 C 2 Estimate Memory Use...
Page 422: ...Publication 1756 UM001E EN P August 2002 D 2 Determine When Data Is Updated Notes...
Page 424: ...Publication 1756 UM001E EN P August 2002 E 2 Reconfigure an I O module Notes...
Page 428: ...Publication 1756 UM001E EN P August 2002 4 Index...
Page 429: ...Publication 1756 UM001E EN P August 2002 Index 5 Allen Bradley HMIs...
Page 430: ...Publication 1756 UM001E EN P August 2002 6 Index...
Page 435: ...ControlLogix System User Manual Allen Bradley HMIs...