Publication 1756-UM532A-EN-P - May 2006
A-2
Specifications
EFT/B Immunity
IEC 61000-4-4:
+/-2 kV at 5 kHz on communications ports
Surge Transient Immunity
IEC 61000-4-5:
+/-1 kV line-earth (CM) on communications ports
Conducted RF Immunity
IEC 61000-4-6:
10 Vrms with 1 kHz sine-wave 80%AM from 150 kHz...80 MHz
Magnetic Field Immunity
IEC 61000-4-8:
30 A/m at 50 Hz
Enclosure Type Rating
None (open-style)
Certifications
Attribute
Value
Certifications
(when product is marked)
(1)
c-UL-us UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada. See UL File
E194810.
CE
European Union 89/336/EEC EMC Directive, compliant with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
(1)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and
other certification details.
Environmental Specifications
Attribute
Value
Summary of Contents for ControlLogix 1756-DH485
Page 1: ...ControlLogix DH 485 Communication Module 1756 DH485 User Manual...
Page 8: ...Publication 1756 UM532A EN P May 2006 Preface ii Notes...
Page 18: ...Publication 1756 UM532A EN P May 2006 1 10 1756 DH485 Module Overview Notes...
Page 32: ...Publication 1756 UM532A EN P May 2006 2 14 Overview of the DH 485 Network Notes...
Page 102: ...Publication 1756 UM532A EN P May 2006 B 6 Troubleshoot the 1756 DH485 Module Notes...
Page 106: ...Publication 1756 UM532A EN P May 2006 iv Index Notes...
Page 109: ......