Publication 1756-UM532A-EN-P - May 2006
Communicate from a Logix Controller to an SLC 5/03 Controller over EtherNet/IP and DH-485 Networks
10-5
This is the Communication tab for the remote message.
Path Item
Description
series_A
This means go to the
backplane to slot 5 where
the 1756-ENBT named
Series_A is located.
Series A is defined as
backplane 1, slot 5.
2
EtherNet/IP port.
100.100.100.7
The remote 1756-ENBT.
1
Go to the backplane of the
remote 1756 chassis.
14
Go to the slot location of
the 1756-DH485 module.
2
Go out Channel A of the
1756-DH485 module.
1
Go to Node 1 or the
location of the SLC 5/03
controller.
TIP
You do not need to create a routing
table when your communication
method is CIP messaging.