Rockwell Automation Publication 5069-IN003C-EN-P - December 2016
15
5069 Compact I/O EtherNet/IP Adapters
Connect SA AC Power to the 5069-AENTR Adapter
Before you connect an external power source to the Power RTB
terminals that are used for SA power, make sure that the power source
is properly sized. For example, if the total SA power current draw is
7 A, you can use an SA power supply that is limited to 7 A.
1. Verify that the SA power source is not powered on.
2. Strip insulation from the wires that you connect to the RTB.
3. Connect the L1/AC(+) wire from the external SA AC power
source to the +/L terminal.
4. Connect the L2/N/AC(—) wire from the external SA AC
power source to the —/N terminal.
5. Connect a wire from an earth ground location to the
terminal on the RTB.
Disconnect Wires from RTBs
If necessary, complete the following tasks to disconnect wires from any
RTB on the adapter. The actions apply to every catalog number for an
RTB type.
For example, the graphic shows the 5069-RTB4-SCREW RTB.
However, you complete the same actions to disconnect wires for any
Screw-type RTB.
WARNING:
If you connect or disconnect wiring while the field-
side power is on, an electric arc can occur. This could cause an
explosion in hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.
RTB Type
Action
Screw
Strip 10 mm (0.39 in.) of insulation from the wires.
Spring
Strip 10 mm (0.39 in.) of insulation from the wires.
RTB Type
Action
Screw
1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the
screw to 0.5…0.6 N•m (4.4…5.3 lb•in).
Spring
Push the wire into the terminal.
If the wire is too thin, crimp a wire ferrule on the wire and insert it.
RTB Type
Action
Screw
1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the
screw to 0.5…0.6 N•m (4.4…5.3 lb•in).
Spring
Push the wire into the terminal.
If the wire is too thin, crimp a wire ferrule on the wire and insert it.
5069-RTB5-SPRING RTB
5069-RTB5-SCREW RTB
5069-RTB5-SPRING RTB
5069-RTB5-SCREW RTB
RTB Type
Action
Screw
1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the
screw to 0.5…0.6 N•m (4.4…5.3 lb•in).
Spring
Push the wire into the terminal.
If the wire is too thin, crimp a wire ferrule on the wire and insert it.
TIP
The
symbol denotes an earth ground terminal that
provides a low impedance path between electrical circuits and
earth for protective earth purposes and provides noise
immunity improvement.
We recommend that you use the AWG14 wire type or
equivalent for grounding purposes. Make sure that you
securely connect the ground to proper earth grounding via the
ground bus.
WARNING:
If you connect or disconnect wiring while the field-
side power is on, an electric arc can occur. This could cause an
explosion in hazardous location installations. Be sure that power
is removed or the area is nonhazardous before proceeding.
RTB Type
Action
Screw
1. Turn the screwdriver counter-clockwise to open the terminal.
2. Remove the wire.
Spring
1. Insert and hold a screwdriver in the right-side terminal.
2. Remove the wire.
3. Pull out the screwdriver.
5069-RTB5-SPRING RTB
5069-RTB5-SCREW RTB
Spring-type RTB
Screw-type RTB