background image

14

Rockwell Automation Publication 5069-IN003C-EN-P - December 2016

5069 Compact I/O EtherNet/IP Adapters

4. Connect the 24V DC(—) wire from the external power supply 

to the — terminal.

Connect SA DC Power to the 5069-AENTR Adapter

Before you connect an external power source to the Power RTB 
terminals that are used for SA power, make sure that the power source 
is properly sized. For example, if the total SA power current draw is 
7 A, you can use an SA power supply that is limited to 7 A.

1. Confirm that MOD power and all sources of SA power are 

turned off.

2. Strip insulation from the wires that you connect to the RTB.

3. Connect the DC(+) wire from the external DC power supply 

to the +/L terminal.

4. Connect the DC(—) wire from the external SA DC power 

supply to the —/N terminal.

5. Connect a wire from an earth ground location to 

the

terminal on the RTB. 

RTB Type

Action

Screw

1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the 

screw to 0.5…0.6 N•m (4.4…5.3 lb•in).

Spring

Push the wire into the terminal. 
If the wire is too thin, crimp a wire ferrule on the wire and insert it.

WARNING: 

If you connect or disconnect wiring while the field-

side power is on, an electric arc can occur. This could cause an 
explosion in hazardous location installations. Be sure that power is 
removed or the area is nonhazardous before proceeding.

RTB Type

Action

Screw

Strip 10 mm (0.39 in.) of insulation from the wires.

Spring

Strip 10 mm (0.39 in.) of insulation from the wires.

RTB Type

Action

Screw

1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the 

screw to 0.5…0.6 N•m (4.4…5.3 lb•in).

Spring

Push the wire into the terminal. 
If the wire is too thin, crimp a wire ferrule on the wire and insert it.

5069-RTB5-SPRING RTB

5069-RTB5-SCREW RTB

5069-RTB5-SPRING RTB

5069-RTB5-SCREW RTB

RTB Type

Action

Screw

1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the 

screw to 0.5…0.6 N•m (4.4…5.3 lb•in).

Spring

Push the wire into the terminal. 
If the wire is too thin, crimp a wire ferrule on the wire and insert it.

RTB Type

Action

Screw

1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the 

screw to 0.5…0.6 N•m (4.4…5.3 lb•in).

Spring

Push the wire into the terminal. 
If the wire is too thin, crimp a wire ferrule on the wire and insert it.

TIP

The

symbol denotes an earth ground terminal that 

provides a low impedance path between electrical circuits and 
earth for protective earth purposes and provides noise 
immunity improvement.

We recommend that you use the AWG 14 wire type or 

equivalent for grounding purposes. Make sure that you 
securely connect the ground to proper earth grounding via the 
ground bus.

WARNING: 

Protection is relied upon an external branch circuit 

protection.

5069-RTB5-SPRING RTB

5069-RTB5-SCREW RTB

5069-RTB5-SPRING RTB

5069-RTB5-SCREW RTB

Summary of Contents for Compact I/O 5069 series

Page 1: ...tion on how to use 5069 Compact I O EtherNet IP adapters including the compatible Logix5000 controllers and Logix Designer application versions see the publications that are listed in Additional Resources on page 19 SummaryofChanges This publication was revised to include information about the 5069 AENTR adapter Topic Page Summary of Changes 1 About the Adapters 5 Install a 5069 Compact I O System...

Page 2: ...e code de pratique en vigueur Si cet équipement est utilisé d une façon qui n a pas été définie par le fabricant la protection fournie par l équipement peut être compromise 㭒㦮 a G㩲䛞G 䂮 SG 㩫 SG㧧 G G㥶㰖G 㑮䞮 G㩚㠦G Gⶎ G䙂䞾䞮㡂G 䂮 SG 㩫G G㧧 㠦Gὖ䞲G㺎ἶG㧦 G 㦮Gⶎ 㦚G 㔲G㧓ἶG㑯㰖䞮 㕃㔲㡺 UG 㣿㧦 G Gὖ G 㩫 SG G G䚲㭖㠦 G㣪ῂ䞮 G 䟃㠦G 䟊G 㔲G 䂮G G G㰖䂾㦚G㑯㰖䟊㟒G䞿 U 䂮 SG㫆㩫 SGṖ SG 㣿 SG㫆Ⱃ SG 䟊 SG㥶㰖 㑮G G G㧧㠛㦖Gὖ G 㩫㠦G G㩗㩞䞲Gᾦ㥷㦚G 㦖G 㣿㧦 G䐋䟊 ⰢG㑮䟟䟊㟒G䞿...

Page 3: ...r les autorités locales qualifiées au moment de l installation WARNING EXPLOSION HAZARD Donotdisconnectequipmentunlesspowerhasbeenremovedortheareais known to be nonhazardous Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous Secure any external connections that mate to this equipment by using screws sliding latches threaded connect...

Page 4: ...mming purposes only and not intended for permanent connection Do not use the USB port in hazardous locations Prevent Electrostatic Discharge ATTENTION Thisequipmentissensitivetoelectrostaticdischarge whichcancauseinternaldamageandaffectnormaloperation Followtheseguidelineswhen you handle this equipment Touch a grounded object to discharge potential static Wear an approved grounding wriststrap Do n...

Page 5: ...ations Besurethat power is removed or the area is nonhazardous before proceeding WARNING Do not use the USB port in hazardous locations 5069 AEN2TR EtherNet IP adapter only IMPORTANT Any illustrations charts sample programs and layout examples shown in this publication are intended solely for the purposes of example Since there are many variables and requirements associated with any particular ins...

Page 6: ...NG kit contains the 5069 RTB5 SPRING RTBs We recommend that you order only the RTB type that your system requires External power supply for Module MOD Power A power supply that is adequately sized to provide MOD power that is system side power to the 5069 Compact I O system For more information see System Power Considerations on page 8 External power supply for Sensor Actuator SA Power A power sup...

Page 7: ...in 130 31 mm 5 13 in 101 66 mm 4 00 in ATTENTION This product is grounded through the DIN rail to chassis ground Use zinc plated chromate passivated steel DIN rail to assure proper grounding The use of other DIN rail materials for example aluminum or plastic that can corrode oxidize or are poor conductors can result in improper or intermittent grounding Secure DIN rail to mounting surface approxim...

Page 8: ...9CompactI Osystem MOD power is provided through the MOD power RTB and passed across the MOD power bus You must limit the MOD power source to 10 A max at 18 32V DC Confirm that the external MOD power supply is adequately sized for the total MOD power bus current draw in the system Forexample ifthetotalMODpowercurrentdraw includingcurrentinrush requirements is5A youcanuseaMODpowersupplythatislimited...

Page 9: ... 3 Position the adapter so that the back of it faces the DIN rail 4 Press the adapter against the DIN rail until you hear a click 5 Confirm that the adapter is latched securely ConnectPowertothe5069 AEN2TRAdapter Before you connect MOD power or SA power to a 5069 AEN2TR adapter complete the following tasks Read System Power Considerations on page 8 Confirm that the external power supplies that sup...

Page 10: ...Power RTB is used only on the 5069 AEN2TR adapter IMPORTANT Your application can require a power control device for example a switch between the external 24V DC power source and the adapter to control when the module is powered If so you must install the power control device at theVDC terminal on the removable terminal block If you install the power control device at theVDC terminal the adapter ca...

Page 11: ...t connect or disconnect the RemovableTerminal Block RTB while power is applied Be sure that power is removed before proceeding IMPORTANT The SA Power RTB is used only on the 5069 AEN2TR adapter WARNING If you connect or disconnect wiring while the field side power is on an electric arc can occur This could cause an explosioninhazardouslocationinstallations Besurethatpoweris removed or the area is ...

Page 12: ... cause an explosioninhazardouslocationinstallations Besurethatpoweris removed or the area is nonhazardous before proceeding RTBType Action Screw Strip12 mm 0 47 in of insulation from the wires Spring Strip 10 mm 0 39 in of insulation from the wires RTBType Action Screw 1 Insert the wire into the terminal 2 Turn the screwdriver to close the terminal on the wire Torque the screw to 0 4 N m 3 5 lb in...

Page 13: ...ty Do not connect or disconnect the RemovableTerminal Block RTB while power is applied Be sure that power is removed before proceeding IMPORTANT The Power RTB is used only on the 5069 AENTR adapter MOD POWER SA POWER ADAPTER 5069 AENTR 2 1 Compact I O OK NET LINK 1 LINK 2 WARNING EXPLOSION HAZARD Do Not Disconnect While Circuit is Live Unless Area Is Known To Be Non Hazardous A VERTISSEMENT RISQUE...

Page 14: ...eeding RTBType Action Screw Strip 10 mm 0 39 in of insulation from the wires Spring Strip 10 mm 0 39 in of insulation from the wires RTBType Action Screw 1 Insert the wire into the terminal 2 Turn the screwdriver to close the terminal on the wire Torque the screw to 0 5 0 6 N m 4 4 5 3 lb in Spring Push the wire into the terminal If the wire is too thin crimp a wire ferrule on the wire and insert ...

Page 15: ...river to close the terminal on the wire Torque the screw to 0 5 0 6 N m 4 4 5 3 lb in Spring Push the wire into the terminal If the wire is too thin crimp a wire ferrule on the wire and insert it RTBType Action Screw 1 Insert the wire into the terminal 2 Turn the screwdriver to close the terminal on the wire Torque the screw to 0 5 0 6 N m 4 4 5 3 lb in Spring Push the wire into the terminal If th...

Page 16: ...odules in the system install the end cap 1 Align the end cap with interlocking pieces on the adapter 2 Push the end cap toward the DIN rail until it locks into place PowertheSystem After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB WARNING If you connect or disconnect the communication cable with power applied to this module or a...

Page 17: ...onnect the module while power is applied Be sure that power is removed before proceeding IMPORTANT When you remove MOD power from a 5069 Compact I O EtherNet IP adapter you shut down power to all modules in the 5069 Compact I O system That is all system side is removed When you remove SA power from the 5069 Compact I O EtherNet IP adapter all field side power that is provided by the adapter is rem...

Page 18: ...tinuous Basic InsulationType SA and MOD Power to Backplane 300V continuous Basic InsulationType SA to MOD Power 300V continuous Basic InsulationType Ethernet to Backplane Type tested at 1500V AC for 60 s 300V continuous Double InsulationType Ethernet to MOD Power 300V continuous Double InsulationType Ethernet to SA Power Type tested at 4242V DC for 60 s No isolation between Ethernet ports Recommen...

Page 19: ...ion ENET RM002 Describes how to use EtherNet IP adapters with Logix5000 controllers and communicate with other devices on the EtherNet IP network EtherNet IP Embedded SwitchTechnology Application Guide publication ENET AP005 Describes how to install configure and maintain linear and Device Level Ring DLR networks by using Allen Bradley EtherNet IP devices that are equipped with embedded switch tec...

Page 20: ...ve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents du ra du002_ en e pdf Technical Support Center Knowledgebase Articles How toVideos FAQs Chat User Forums and Product Notification Updates https rockwellautomation custhelp com LocalTechnical Suppo...

Reviews: