Bulletin 900-CONV
Interface Converter
25
External Connections
RS-485 Connection
❄
✶
If RS-485 is selected as the communications method (i.e., pin 9 of the DIP switch is set to OFF), terminals 8 and 9, and terminals 11 and 12 are connected
internally.
7
A 100…240 V AC, 24 V AC, or 24 V DC (not polarity sensitive) input power supply is required.
Function
Terminal
Number
Name
Signal
Direction
Explanation
For connecting the operating power supply
1 and 4
PWR
—
100…240V AC or 24 V AC/DC model
Connection terminals for RS-232C
communications with master device (DIP
switch pin 8: OFF)
3
SG
—
Connect to signal ground.
5
SD
Input
Receives data from SD of the master device.
6
RD
Output
Sends data to RD of the master device.
Used for RS-485 communications with
slave device (DIP switch pin 9: OFF)
8
RDA (–)
Input/
output
SD and RD for RS-485 (cold side)
Terminals 8 and 9 are connected internally when pin 9 of the DIP switch is set to
OFF.
9
SDA (–)
11
RDB (+)
Input/
output
SD and RD for RS-485 (hot side)
Terminals 11 and 12 are connected internally when pin 9 of the DIP switch is set to
OFF.
12
SDB (+)
Note:
Terminals 2 and 10 are not used.
Terminal Specifications
Make sure to check the input and output specifications for the signal pins of connected devices before connecting the terminals.
Connection to an RS-232C Master Device
Set the same communications conditions (baud rate, stop bits, data length, and parity) for the master device, the Interface Converter, and
slave devices.
‡
With RS-485 communications, connect a terminating resistance (120
Ω
, 1/2 W recommended) to both ends of the communications link/network.
§
The Bulletin 900-TCx communications number must be set.
♣
A pre-fabricated 3 m RS-232 cable with a 9-pin female D-shell connector on one end and three flying leads at the other is available from Allen-Bradley
(Cat. No. 900-CP1X).
³
RS-485 allows connecting 32 devices.
a
Use a commercially available USB cable
To use the USB mode requires the download of free software into your PC. This software can be found at the
Bulletin 900 Temperature Controller website:
http://www.ab.com/industrialcontrols/products/relays_timers_and_temp_controllers/single_loop_temp-
heater_controllers/900tc.html
Once at this site, go to "Get Software" (upper right of screen) and click on "Virtual Communications Port USB Driver" and follow the instructions.
‡§
✟
900Bu
i
l
der
L
i
t
e
o
r
Summary of Contents for Bulletin 900-CONV
Page 1: ...SELECTION GUIDE BULLETIN 900 TC Single Loop Electronic Temperature Process Controllers...
Page 2: ......
Page 29: ......