Bulletin 900-TC
Single-Loop Temperature/Process Controller
18
Wiring Terminals
Note:
Input power supply available: 100…240 V AC, or 24 V AC/DC
Bulletin 900-TC32
Bulletin 900-TC32 — Wiring Terminals
Wiring Terminals — General Guidelines
y
The voltage output (SSR control output) is not electrically isolated from the controller’s internal circuits. When using a grounded
thermocouple, do not connect the control output terminals to earth ground. If the control output terminals are connected to earth ground,
errors will occur in the measured temperature values as a result of ground loop leakage current.
y
Standard insulation ratings exist between any of the following: power supply terminals, input terminals, output terminals, and
communication terminals. If reinforced insulation is required, provide additional insulation, such as spatial distance or material insulation, as
defined by IEC 60664.
y
Separate input leads and power lines to protect the Bulletin 900-TC8/900-TC16 and its lines from external noise.
Bulletin 900-TC16 — Wiring Terminals
Relay Output
Voltage Output
−
+
+
−
+
Auxiliary Outputs
Control output 1
Aux1/
Heater burnout alarm/
Input error output
Aux 2
Analog input
Current Output
Infrared
temperature
sensor
Platinum
resistance
thermometer
The input power supply depends on the power
supply specification of the Controller and is either
100 to 240 VAC or 24 VAC/DC (no polarity).
6
7
8
9
10
11
12
13
14
15
1
3
2
4
5
B
Pt
TC
A
B
V
mA
6
7
8
1
2
1
2
1
2
−
+
4 to 20 mA DC/
0 to 20 mA DC
−
+
12 VDC
21 mA
Input power supply
Triac Output
1
2
Option Unit
Terminals
Bulletin 900-TC16
Option Unit Terminals,
refer to page 19.