Chapter 5
Configure and Replace Safety Modules
Edit the 1756-IB16S Module
Configuration Categories
These categories are available when you configure a 1756-IB16S module:
•
•
Input Points Category
The Input Points category is only available if you choose This Controller for the
Configured By parameter on the Module Definition dialog box. You must
configure each point to use it in a Safety application. The inputs are disabled by
default.
Point Mode
Determines the operation mode of the output point.
• Not Used - The output point is disabled.
• Safety - The output point is enabled.
• Safety Pulse Test - The output point is enabled and a pulse test is
periodically performed on the output to make sure the output is
functioning. The pulse test only occurs when the point is On. The pulse
has a fixed state of periodic.
The default value is Not Used.
Test Source
Displays the Test Source values. There is a value for each point, 00-15. When
Safety Pulse Test is selected in Point Mode, the value appears according to the
point number.
Input Delay Time (ms)
For more information on input delay times, see