84
Rockwell Automation Publication 1756-UM013B-EN-P - October 2019
Chapter 5
Configure and Replace Safety Modules
Module Definition
Module Definition parameters are available on the General tab of the Module
Properties dialog box in the Logix Designer application project.
describes the parameters on the Module Definition dialog box.
describes the parameters on the Module Definition dialog box.
1756-IB16S
1756-OBV8S
Table 25 - Module Definition Parameters
Parameter
Definition
Available Choices
Series
Module hardware series
Module-specific
Revision
Module firmware revision, including major and minor revision levels
Module-specific
Electronic Keying
Software method by which you reduce the possibility of using the wrong device in a control system.
For more information, see the following:
•
• Electronic Keying in Logix5000 Control Systems Application Technique, publication
• Exact Match
• Compatible Module
Configured By
Determines the following for the module type you configure:
• Which controller tags are generated when configuration is complete
• Whether you can choose an Output Data type - Output module only
• Whether you can choose an Output Mode - Output module only
• This Controller
• External Means
(1)
Input Data
Determines what type of input data is exchanged between the module and the controller.
Creates all controller tags specific to the module type being used.
IMPORTANT
: The 1756-OBV8S output module exchanges input data with the controller.
• Safety data
• Safety packed data
Output Data - 1756-OBV8S
module only
Determines what type of output data is exchanged between the module and the controller.
The available choices are dictated by the Configured By parameter choice.
• None - If Configured By is
External Means.
• Safety data and Safety
packed data - If
Configured By is This
Controller.
Output Mode - 1756-OBV8S
Determines how the outputs are used. That is, one of the following:
• Sourcing outputs. In this case, you connect the external device to only the sourcing point on an output
channel.
• As connection pairs. In this case, you connect the external device to both the sourcing and sinking points
of the bipolar output pair.
• Sourcing
• Bipolar
(1) Controller and module establish communication without the controller sending any configuration or output data to the module. A full input data connection is established but depends on the
connection between the owner-controller and the module.