Rockwell Automation Publication 1756-UM013B-EN-P - October 2019
51
1756-IB16S Input Module Features
Chapter 3
Off to On Delay
An input signal is treated as Logic 0 during the Off to On delay time after the
rising edge of the input contact.
The input turns on only if the input contact remains on after the Off to On delay
time has elapsed. This setting help prevent rapid changes of the input data due to
contact bounce.
You can delay the Off to On transition by the following times:
• 0 ms
• 1 ms
• 2 ms
• 5 ms
• 10 ms
• 20 ms
• 50 ms
Figure 10 - Off to On Delay
ON
OFF
ON
OFF
Input Signal
Safety Input
Network Data
Off to On Delay