1756-OBV8S Output Module Features
Chapter 4
Fault and Status Reporting
The output modules multicast fault and status data with channel data to the
owner and listening controllers. The data is returned via module tags that you can
monitor in your Logix Designer application.
lists tags that are used on the 1756-OBV8S module.
For more information on fault reporting, see Appendix A,
Configurable Channel-level
Output State in Program
Mode or Fault Mode
You can configure individual output channels to specific states when the module
is in Program mode or Communications Fault mode. These output states are
available:
• Off
• Hold
To see how to configure the output states in Program mode or Fault mode, see
Edit the 1756-OBV8S Module Points Category on page 90
IMPORTANT
For more information on the valid values for each tag in
Module Tag Definitions on page 113
.
Table 24 - 1756-OBV8S - Fault and Data Status
Data Type
Tag Name
Triggering Event That Sets
Fault
ConnectionFaulted
(1)
The owner-controller loses its connection to the module.
Ptxx.Fault
The point data quality is bad or the channel is set to Not Used.
Ptxx.ShortCircuit
A short circuit condition exists on the point.
Ptxx.FieldPowerOff
A field power lost condition exists on the point.
Status
RunMode
The module is in Run Mode.
DiagnosticActive
Indicates if any diagnostics are active or if the prognostics threshold is reached.
DiagnosticSequenceCount
The count increments each time that a diagnostic condition is detected or removed.
Ptxx.Readback
A 24V DC power source is connected to the output circuit.
Ptxx.Uncertain
The point data can be imperfect.
Ptxx.Status
The point state transitions from normal to faulted or faulted to normal.
(1) This tag provides module-wide data an affects all channels simultaneously.
WARNING:
The selection of “Hold” for Output State During Program Mode and
Communications Fault Mode prevents the output point from going to the safe
state, making the output point not suitable for a SIL or PL rated safety function.
Set Output State During Program Mode and Communications Fault Mode to
"Off" to allow points to go to safe state.
TÜV Rheinland has approved GuardLogix 5580 and Compact GuardLogix 5380
controller systems for use in safety-related applications where the de-energized
state is always considered to be the safe state. You must ensure each configuration
of the safety IO module is set for "Off" under the Output State During Program
Mode and Communications Fault Mode selection to consider those output points as
part of any equipment's safety function.