1.5 AMF601 Installation
1.6 AMF900 Installation
Installation Note:
1) The pipe flange should be welded well before installing flowmeter. It's not allowed to weld flange after flowmeter is
installed. And welding part of pipe flange should be flat, having no sharp residue. Otherwise liner will be damaged. After
flowmeter is installed, if other places in pipe needs to be welded, flowmeter's power must be shut down.
2) Usually there will be weld residues in newly installed pipe. Before installing the sensor, those residues should be
cleaned off so as to avoid liner damage
3) If pipe is not alligned well or sloped, there will be leakage problem or liner damage.