Installation 

2

WARNING 

The equipment described in this manual is designed to operate with 
LP-gas, a flammable fuel under pressure.  The nature of the 
application involves inherent hazards that could result in injury.  
ONLY a trained and fully qualified person should service this 
equipment. 

INSTALLATION PROCEDURE 

1.

Gas must pass through the FILTAIRE for it to work properly.  Mount it
downstream of the vaporizer and the first stage regulator.  Mount it level for
the filter to work efficiently.

2.

Insulation may be required depending on gas pressure, outside temperature
and system requirements.

3.

The FILTAIRE must have a bypass around the filter with shut-off valves for
removal and cleaning.  

See the accompanying diagram

.

4.

The filtered impurities must be drained to proper containers.  Make
provisions for draining and disposing of the material safely.

5.

A customer supplied relief valve must be installed to protect Filtaire and
downstream equipment from potential overpressure damage.

Figure 2 – Installation 

FILTMAN2.dwg 

Summary of Contents for FILTAIRE OIL DEMISTER

Page 1: ...al Innovative liquid vaporizing and gas mixing solutions 151 South Michigan Street Seattle Washington USA 98108 Tel 206 789 5410 Fax 206 789 5414 Web www algas sdi com FILE MANUAL PN 52634 REV 01 28 1...

Page 2: ...rough the system blow down drain Residual heavy end hydrocarbons with boiling points higher than pure LPG are trapped by the filter and fall to the bottom for removal A complete FILTAIRE system consis...

Page 3: ...it downstream of the vaporizer and the first stage regulator Mount it level for the filter to work efficiently 2 Insulation may be required depending on gas pressure outside temperature and system req...

Page 4: ...Installation 2 4 Algas SDI Operations and Maintenance Manual P N 52634 Figure 3 General Equipment FILTMAN4 dwg...

Page 5: ...e system Those using the system must establish the draining schedule A general rule of thumb used to help establish the draining schedule is to measure the amount of heavy end hydrocarbons drained aft...

Page 6: ...ccumulated significant amount of residue and must be cleaned to keep on operating properly In general a FILTAIRE must be cleaned every 6 months The frequency of cleaning will greatly depend on the qua...

Page 7: ...cleaning area 5 Cap the inlet 6 Fill the unit with kerosene or a similar light solvent and allow it to soak for 24 hours 7 Reverse flush the unit flush from outlet flange with kerosene until the Kero...

Page 8: ...8 Algas SDI Operations and Maintenance Manual P N 52634 Table 2 Maintenance Form DATE DATE DRAINED AMOUNT DRAINED PRESSURE DATE CLEANED SPARE PARTS ASDI PN 30897 Float Switch ASDI PN 30641 Pressure Ga...

Page 9: ...can be used to shut down the system if liquid continues to increase in the reservoir This same system can be used to provide an additional safety that will prevent liquid propane from getting into con...

Page 10: ...Options 5 10 Algas SDI Operations and Maintenance Manual P N 52634 Figure 4 Options A FILTMAN5 dwg...

Reviews: